4
3. Installation
3. 1 Unpacking Inspection
1. Open the packing box of UPS and take it out, visually examine the unit for transit damage.
2. Check against the accessory lists that the accessories of the UPS are present. (Refer to Table 9-1).
3. Make sure the model is what you wanted from the nameplate on the rear panel.
4. If the UPS arrives damaged, or there is any missing accessory or other question above, please contact the
distributor immediately.
3. 2 Installation Notes
1. When locating the UPS, make sure there is no hazardous objects such as water, inflammable
gas, corrosive agents and so on around the UPS, and that the installation environment meets the
specifications.
2. The UPS should not be placed on a side. The air inlet port at the front panel and the outlet port on the
rear panel and two side panels should not be blocked so as to ensure good ventilation.
3. In case if the UPS is unpacked, installed and used at very low temperatures, condensations of water drops
may appear. It is necessary to wait until the UPS fully dried inside out before proceeding to installation
and use. Otherwise, they may be a risk of electric shock.
4. Place the UPS near the utility power source outlet which supplies power to the UPS. In any emergency,
switch off the main input socket, cut off the battery voltage input. All power sockets must be connected
with ground protection.
3. 3 Cable Connection
3.3.1 Connecting Input and Output Cables
1.
Input cable connection
If the UPS is connected via the power cable, please
use a proper socket with over current protection,
and pay attention to the capacity of the socket:
over 10A for 1K/L, over 16A for 2K/L and
3K/L. side of input wiring has been fixed with
the UPS, and the other side is just need to plug
into the input socket. The wiring configuration
is shown in the following diagram.
2.
Output cable connection
The output of 1K/L, 2K/L, 3K/L all available to
uses sockets. The total output power shall not
exceed 1kVA/0.8kW/0.9kW, 2kVA/1.6kW/1.8kW,
3kVA/2.4kW/2.7kW. Simply plug the load power
cable to the output sockets of UPS to complete
connection as shown in the following diagram.
• Figure 3-1 Connection Method of Input
• Figure 3-2 Connection method of output
LOAD
Summary of Contents for Venus Smart 1K
Page 20: ......