3. Installation                                                                                                                        

3. 1 Unpacking Inspection

  1. Open the packing box of UPS and take it out, visually examine the unit for transit damage.

  2. Check against the accessory lists that the accessories of the UPS are present. (Refer to Table 9-1).

  3. Make sure the model is what you wanted from the nameplate on the rear panel.

  4. If the UPS arrives damaged, or there is any missing accessory or other question above, please contact the 

 

    distributor immediately.

3. 2 Installation Notes

  1. When  locating  the  UPS,  make  sure  there  is  no  hazardous  objects  such  as  water,  inflammable 

 

    gas,  corrosive  agents  and  so  on  around  the  UPS,  and  that  the  installation  environment  meets  the 

 

    specifications.

  2. The UPS should not be placed on a side. The air inlet port at the front panel and the outlet port on the  

    rear panel and two side panels should not be blocked so as to ensure good ventilation.

  3. In case if the UPS is unpacked, installed and used at very low temperatures, condensations of water drops  

    may appear. It is necessary to wait until the UPS fully dried inside out before proceeding to installation 

 

    and use. Otherwise, they may be a risk of electric shock.

  4. Place the UPS near the utility power source outlet which supplies power to the UPS. In any emergency, 

 

    switch off the main input socket, cut off the battery voltage input. All power sockets must be connected 

 

    with ground protection.

3. 3 Cable Connection

3.3.1 Connecting Input and Output Cables

 1. 

Input cable connection

    If the UPS is connected via the power cable, please  

    use a proper socket with over current protection,  

    and pay attention to the capacity of the socket: 

 

    over  10A  for  1K/L,  over  16A  for  2K/L  and

 

     3K/L.  side  of  input  wiring  has  been  fixed  with 

 

    the UPS, and the other side is just need to plug 

 

    into  the  input  socket.  The  wiring  configuration 

 

    is shown in the following diagram.

 
 2. 

Output cable connection

 

    The output of 1K/L, 2K/L, 3K/L all available to  

    uses sockets. The total output power shall not  

 

  exceed 1kVA/0.8kW/0.9kW, 2kVA/1.6kW/1.8kW, 

 

  

3kVA/2.4kW/2.7kW. Simply plug the load power

 

    cable to the output sockets of UPS to complete 

     connection as shown in the following diagram.

• Figure 3-1 Connection Method of Input 

• Figure 3-2 Connection method of output

LOAD

Summary of Contents for Venus Smart 1K

Page 1: ...HUPHOTIC CO LTD ENERGY WAVE CO LTD CHUPHOTIC ELECTRONICS CO LTD 949 Moo 9 Sumrong Nue Muang Samutprakarn Samutprakarn 10270 Tel 02 186 3011 Fax 02 186 3018 19 Website www chuphotic com E mail ups chup...

Page 2: ...g Inspection 4 3 2 Installation Notes 4 3 3 Cable Connection 4 5 4 Operation LCD model 6 10 4 1 Operation Display Panel 6 4 2 Operation Mode 6 8 4 3 Operating Instructions 9 10 5 Maintenance 10 11 5 1...

Page 3: ...Do not short the positive and negative electrodes of battery Otherwise it may cause electric shock or fire 6 Do not plunge or insert any objects into the air vents and other inlets 7 Do not store or...

Page 4: ...el Remark 1K With a 1A internal charger and 3 build in batteries of 12V 7AH 2K With a 1A internal charger and 6 or 8 build in batteries of 12V 7AH 3K With a 1A internal charger and 8 build in batterie...

Page 5: ...battery through the DC DC converter 5 Bypass It is very important in the UPS system In the event of a UPS fault that will not lead to UPS shutdown the load will be automatically transferred to the byp...

Page 6: ...o wait until the UPS fully dried inside out before proceeding to installation and use Otherwise they may be a risk of electric shock 4 Place the UPS near the utility power source outlet which supplies...

Page 7: ...t on the rear panel of the UPS to complete the connection procedure Note The length of the external battery cable is 1 6 m If users need a longer one please consult the distributor There is a limit to...

Page 8: ...ndicators The LED indicators contains Bypass indicator utility power indicator Inverter indicator Battery indicator The definition of each indicator is the same as LED panel refer to table 4 1 Table 4...

Page 9: ...oads connected to the UPS less than 100 capacity of the UPS 3 If the battery indicator blinks it indicates that no battery is connected to the UPS or battery voltage is too low You should check if bat...

Page 10: ...er another circularly When the battery is fully charged all the level icons are turned on 1 When operating in bypass mode the UPS beeps every 2 minutes If the Function key is pressedfor more than 2 se...

Page 11: ...switch to output page by pressing function button When a warning occurred the fault icon blinks every second and users can switch to the alarm display page shown as the figure 5 6 to check the warning...

Page 12: ...s shown on the front panel and no output is available from the UPS outlets system completely power down 2 Completely power down the UPS from Battery mode Press the OFF button persistently for more tha...

Page 13: ...rature between 15o C and 25o C 3 If the UPS has not been used for a long period charging is recommended at the intervals 3 months 4 Batteries should not be replaced individually 5 Under normal conditi...

Page 14: ...tributor or service center The 8 utility power LED blinks in normal mode Maybe reversed polarity L N of site wiring or disconnect with ground or the voltage between neutral wiring to protective ground...

Page 15: ...or Service center F05 On constantly Beep continuously Internal fault Please contact the distributor or Service center F06 On constantly Beep continuously Internal fault Please contact the distributor...

Page 16: ...every second Battery voltage low The UPS output will be cut off please switch to the backup power A03 Beep once every second UPS power on abnormal Check the battery of the UPS connected properly A05...

Page 17: ...Standard Charge current 1A 6 5A 1A 5 5A 1A 5 5A Crest factor 3 1 1 The output frequency synchronizes with the input frequency when the input frequency is in the range of 45Hz 55Hz 2 The output freque...

Page 18: ...IEC61000 4 4 LEVEL4 Surge IEC61000 4 5 LEVEL4 7 Specifications 7 2 Mechanical Item Normal range Ambient temperature 0 C 45 C Environment humidity 0 90 No condensation Altitude Lower than 1000m no dera...

Page 19: ...odel Intelligent monitor software CD 1 User Manual 1 Serial communication cable 1 UPS 1 Intelligent monitor software CD 1 Long backup time Model User Manual 1 External Battery Cable 1 Serial communica...

Page 20: ......

Page 21: ...Service center please Call 02 1863011 AUTO...

Reviews: