![Chuphotic Venus Smart 1K User Manual Download Page 17](http://html1.mh-extra.com/html/chuphotic/venus-smart-1k/venus-smart-1k_user-manual_2606433017.webp)
15
7. Specifications
7.1 Electrical
Model
VNS1050/L
VNS2000/L
VNS3000/L
Rating
PF 0.8
1050VA/840W
2000VA/1600W
3000VA/2400W
PF 0.9
1050VA/945W
2000VA/1800W
3000VA/2700W
Input
Output
Battery
Output
frequency
Inverter overload
capacity (Utility
power, 25
o
C)
Transfer time
Normal
mode
Battery
mode
Input system
Single phase & earth ground
Voltage range
(90±5)VAC~ (300±5)VAC
Output system
Single phase & earth ground
Batteries voltage
36VDC
72VDC/96VDC
96VDC
Rated voltage
220VAC
Battery quantity
3
None 6/8 None 8 None
Power factor
>0.99
Battery Type
Voltage precision
±1%
Backup Time (25ºC)
Full load≥5min (Standard)
Charge current
1A
6.5A 1A 5.5A 1A 5.5A
Crest factor
3:1
1. The output frequency synchronizes with the input frequency when the
input frequency is in the range of 45Hz~ 55Hz.
2. The output frequency is 50Hz when the input frequency is not in the
range of 45Hz~ 55Hz.
3. Can be set as 60Hz.
100% ± 5% < Load ≤ 105% ± 5% Overload warning only
105% ± 5% < Load < 125% ± 5% 60s transfer to bypass
Load > 125% ± 5%, 30s, Load > 150% 300ms transfer to bypass
0ms (Normal mode←→ Battery mode)
<4ms (Normal mode←→Bypass mode)
Sealed maintenance-free lead –acid battery
of battery voltage 12V/7.5AH or 12V/9.4AH
Power factor
≥0.99
Voltage range
(80±5)VAC~ (286±5)VAC (default: 80VAC~264VAC
of bypass
Could be adjusted by software)
* Note1: Output voltage can be set: 200V/208V/220V/230V/240V.
• All specification are subject to change without prior notice.
Summary of Contents for Venus Smart 1K