viii
CAUTION:
DO NOT dispose of batteries in a fire. The battery may explode. Do not open or
mutilate the battery or battery cabinet. Released electrolyte is harmful to the skin and eyes and is toxic.
WARNING:
Only AUTHORIZED SERVICE PERSONNEL should perform maintenance on or service the UPS system.
Grounding the Unit
CAUTION:
Interruption of the protective grounding conductor or disconnection of the protective earth terminal presents a
potential shock hazard that could result in personal injury and damage to the equipment.
WARNING:
1)
An insulated grounding conductor that is identical in size, insulation material, and thickness to the
grounded and ungrounded branch circuit conductors except that it is green with or without one or more
yellow stripes is to be installed as part of the branch circuit that supplies the unit or system.
2)
The grounding conductor supplied in 1) is to be grounded to earth at the service equipment or, if
supplied by a separately derived system, at the supply transformer or motor-generator set.
3)
The attachment-plug receptacles in the vicinity of the unit or system are all to be of a grounding type,
and the grounding conductors serving these receptacles are to be connected to earth ground at the service
equipment.