42
STORAGE
For extended storage at ambient temperature, < 77°F the batteries should be charged for 5 hours once every 4 months; at higher
storage temperatures, it is advised that this period be reduced to two months.
Make sure the Power Control Unit Breaker is in the OFF position before continuing. Follow the electrical installation procedure in
Chapter 3. Connect the positive and negative External Battery Cabinet Connections if purchased. See chapter 4 for battery
information. Switch the Power Control Unit Circuit Breaker (CB1) from OFF to ON. After 5 hours, turn OFF the Power Control
Unit. For external cabinets, charge for a minimum of 12 hours per battery cabinet. Then remove the UPS connections in the
opposite sequence described in Chapter 3.
Note the date recharging was carried out in the vicinity of the UPS or on its packaging.
CLEANING
Switch off the UPS by pressing the OFF button and disconnect from the mains supply. (see shutdown procedure on page 26)
Do not use scouring powder or plastic-dissolving solutions to clean the UPS.
Do not allow liquid to get inside the UPS.
Make sure that the air vents on the UPS are not obstructed.
Clean air filters as necessary.
Clean the outside of the UPS housing by wiping with a dry or a slightly damp cloth.