CAS 2700-15 Danfoss AK-SC-255 XML
Page
25
of
28
2016 Chipkin Automation Systems
, 3381 Cambie St- Box 211, Vancouver, BC, Canada, V5Z 4R3
Tel:
(866) 383-1657,
Fax:
(416) 915-4024
Website:
www.chipkin.com
7.4 Additional Functionality
7.4.1 Another Method for Changing the IP Address – DHCP
This device supports DHCP, but when shipped, usually a Static IP Address is assigned.
IP = 192.168.1.113
Netmask = 255.255.255.0
Gateway = 192.168.1.1
To enable and to set the Gateway to DHCP, follow these instructions:
1.
Download the tool to change the IP address of the gateway. The tool can be downloaded from:
http://www.chipkin.com/articles/cas-gateway-ip-address-tool
2. When you start this tool it discovers gateways and list them in the right had side ‘Select a
Unit’ area. If the area is blank then click the ‘Search Again’ button. If it remains blank check that
the Ethernet connection is made – is there a green link LED on the RJ45 and on the hub/switch
you are connected to.
3. To set it to DHCP, simply put all fields to 0.0.0.0 and click the ‘Set’ button as displayed in the
image above.