7.2 Diagnostics
Gateway Hardware Diagnostics
1.
Power Led: Green Solid = Normal Condition.
2.
RJ45 LED: Green to show link.
7.3 Trouble-Shooting
7.3.1 Taking Logs
Debugging and Error messages from the Gateway are sent on UDP port 514 to the broadcast IP address:
{255.255.255.255} as plain ASCII text.
You can use Wireshark to take a log of these messages.
A Wireshark log is also very useful for any TCP (like Modbus TCP ) or UDP (like BACnet IP) protocols as
the bytes and messages that are sent and received from the Gateway will also be logged.
Note:
To properly take a log, a hub (not a switch) is required.
For more help with taking logs, please feel free to contact us.
7.3.2 Testing BACnet – Use CAS BACnet Explorer
You have been provided with a USB key to the CAS BACnet Explorer. This key activates the software. It
cannot run without it. If you don’t have your USB key, you can still activate the application – it requires
an internet connection. A video provides help.
http://www.chipkin.com/articles/cas-bacnet-explorer-software-activation-video
You might also want to refer to these articles.
http://www.chipkin.com/articles/cas-bacnet-explorer-usbsoftware-activation-problems
http://www.chipkin.com/cas-bacnet-explorer-licenses-faq
Install and activate the application. Download from here.
http://www.chipkin.com/cas-bacnet-explorer/
Procedure
1.
Start the application
2.
Click Settings
3.
Check IP – uncheck MSTP and Ethernet
4.
Click on the network card you will use.
5.
Click Ok.