C
NA1
Air Circuit Breaker
P-064
P-063
NA1
Air Circuit Breaker
39 41
43 45 47
38
40 42 44
46 48
49
50
7
9
11 13 15 17 19 21 23 25
27 29 31 33 35
37 39 41
43 45
M
Q
F
X
6
8
10 12 14 16 18 20 22 24 26 28 30 32 34
36 38 40 42 44
1
3
5
47
Open
Close
2
4
46
Fault
51
48 50
49
Energy
storage
SA
AX
The secondary circuit wiring for NA1-2000X~6300X with type (3M) intelligent controller and time-delay under-voltage release
The secondary circuit wiring for NA1-2000X~6300X with type (3H) intelligent controller and time-delay under-voltage release
#
#
#
#
#
#
#
#
3 ,4 ,5 : Fault trip contact output(4 common terminal); 6 ,7 ,8 ,9 : Auxiliary contact(normal open)
#
#
#
#
10 ~11 : empty; 12 ~19 are the programmable output terminal. The normal products without these terminals,
but if the customer special ordered, the cost extra added.
3M type acquiescence output:
#
#
#
#
12 ,13 : Signal alarm of load 1 output; 14 ,15 : Signal alarm of load2 output
#
#
#
#
16 ,17 : Self-diagnose alarm; 18 ,19 : Fault trip
#
#
#
20 : PE line; 21 ~24 : Display the voltage of the signal input. The normal products without these terminals,
if the customer special ordered the function meter, the cost extra added.
#
#
#
#
21 : N phase input terminal; 22 ,23 ,24 : A, B, C three phase power input terminal (note the sequence)(Highest-voltage of AC400V)
#
#
25 ,26 Connect to the N phase current transformer or the input terminal of the current leakage transformer.
The normal products without these terminals, if the customer special ordered, the cost extra added.
#
#
#
#
27 ,28 : Under-voltage release(
C
onnected to the main circuit)
; 29 ,30 : Shunt release
#
#
#
#
31 ,32 : Closing release; 33 ,34 : Energy storage indicator
#
#
#
#
34 ,35 : Energy storage motor; 36 ,37 : Under-voltage time delay release
#
#
38 ~51 : Auxiliary contact
Note:
a. Red colored part is to be connected by users
b. When the power system is three phase three wire, directly connect the Un to U2. (If the voltage exceeds 400V,
special explanation when ordered)
Intelligent controller
Emergency
break
Shunt
release
Closing
electromagnet
Energy-
storage
indication
Energy-
storage
motor
Auxiliary switch
To the incoming-line side
Transformer
connected
PE Un U1 U2 U3
Main
circuit
L1
N
PE
1
2
Under-voltage
time-delay
release
Under-voltage
time-delay controller
The auxiliary contact modes for customer use
Ⅰ
Four pairs change-over contacts
SB3
SB1
SB2
SB1: Shunt button; SB2: Under-voltage button
SB3: Making button; Q: Under-voltage release
F: Shunt release; X: Closing release
M: Energy storage motor; XT: Connection terminal
SA: Position switch
1 , 2 : Intelligent controller power input
Note: When the power supply of the intelligent controller
is AC power, the 1 ~2 connects to the AC power directly.
When the power supply is DC power, forbid connecting the
1 ~2 to the DC power directly. Add a DC power supply
module, then the DC power connect to the input terminal
of the DC power supply module, and the 1 ~2 connect to
the output terminal of the DC power supply module,
or else the intelligent controller will be damaged.
#
#
#
#
#
#
#
#
Highest-voltage of AC 400V
39 41
43 45 47
38
40 42 44
46 48
49
50
7
9
11 13 15 17 19 21 23 25
27 29 31 33 35
37 39 41
43 45
Energy
storage
M
Q
F
X
6
8
10 12 14 16 18 20 22 24 26 28 30 32 34
36 38 40 42 44
AX
1
3
5
47
Open
Close
2
4
46
Fault
51
48 50
49
SA
#
#
#
#
3 ,4 ,5 : Fault trip contact output(4 common terminal)
#
#
#
#
6 ,7 ,8 ,9 : Auxiliary contact(normal open)
#
#
#
#
10 ~11 : Communication output; 12 ,13 : Signal alarm of load 1 output
#
#
#
#
#
#
14 ,15 : Signal alarm of load 2 output; 16 ,17 : Breaking signal output; 18 ,19 : Closing signal output
#
#
20 : PE line; 21 : N phase input terminal
#
#
#
22 ,23 ,24 : A, B, C three phase power input terminal (note the sequence)(highest-voltage of AC400V)
#
#
25 ,26 Connect to the N phase current transformer or the input terminal of the current leakage transformer.
The normal products without these terminals, if the customer special ordered, the cost extra added.
ST~DP: DP protocol module. There is no need for the ST-DP protocol module,
if the communication protocol is Modbus-RTV. But when the communication protocol is Profibus-DP,
the ST-DP protocol module is necessary, but the cost extra added.
ST power module IV: power converter (optional components)
ST201: Magnify the signal capacity of the controller. ( optional components)
If the customer special ordered, the cost extra added.
#
#
#
#
27 ,28 : Under-voltage release(
Connected to the main circuit)
; 29 ,30 : Shunt release
#
#
#
#
31 ,32 : Closing release; 33 ,34 : Energy storage indicator
#
#
#
#
34 ,35 : Energy storage motor; 36 ,37 : Under-voltage time delay release
#
#
38 ~51 : Auxiliary contact
Note:
a. Red colored part is to be connected by users
b. When the power system is three phase three wire, directly connect the Un to U2.
(If the voltage exceeds 400V, special explanation when ordered)
Intelligent controller
Emergency
break
Shunt
release
Closing
electromagnet
Energy
storage
indication
Auxiliary switch
To the inconnecting-line side
Transformer
connected
PE Un U1 U2 U3
Special connecting wire
Modbus-RTV
Red
Green
Main
circuit
L1
N
PE
1
2
Under-voltage
time-delay
release
Under-voltage
time-delay controller
Energy
storage
motor
The auxiliary contact modes for customer use
Ⅰ
Four pairs change-over contacts
SB3
SB1
SB2
SB1: Shunt button; SB2: Under-voltage button
SB3: Making button; Q: Under-voltage release
F: Shunt release; X: Closing release
M: Energy storage motor; XT: Connection terminal
SA: Position switch
1 , 2 : Intelligent controller power input
Note: When the power supply of the intelligent controller
is AC power, the 1 ~2 connects to the AC power directly.
When the power supply is DC power, forbid connecting the
1 ~2 to the DC power directly. Add a DC power supply
module, then the DC power connect to the input terminal
of the DC power supply module, and the 1 ~2 connect to
the output terminal of the DC power supply module,
or else the intelligent controller will be damaged.
#
#
#
#
#
#
#
#
PSU-1
~ ~
AC 220V
+
-
DC 24V
D01
DC24V
+
RU-1
D03
D02
-
DI0
D 1
I
D 2
I
D 3
I
D 4
I
D04
Highest-voltage of AC400V
To TO3 busbar
ST-DP
Profibus
24V
NC
GND
D+ D-
D+
D-
Summary of Contents for NA1
Page 1: ...Air Circuit Breaker Leading every step reliable new height ...
Page 2: ...Air Circuit Breaker Leading every step reliable new height ...
Page 3: ......
Page 4: ...Page P 001 Page P 039 ACB Air Circuit Breaker NA8G NA1 ...
Page 45: ...P 041 NA1 Air Circuit Breaker 1 3 4 5 7 8 11 12 13 14 15 ...