100
80
20
120
60
40
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
Is: prospective symmetrical current(of an a.c. circuit)
180
190
200
341
741
2
2
6
I t
(
A s
×
10
)
Is
(
kA
)
2
10. A S curve
. 2 3 .
. 2 2 .
Air Circuit Breaker
Manual energy-storage
Shake with the manual energy-storage handle
up and down about six times to "click".
Inm(A)
NA1-2000
NA1-3200
NA1-4000
NA1-6300
In(A)
630
5
60
2
800
6
60
2
1000
6
80
2
1250
8
80
2
Thickness(mm)
Width(mm)
Number
Busbar
1600
10
80
2
2000
10
80
2
2000
8
100
2
2500
10
100
2
2900
10
100
4
3200
10
100
4
4000/3P
10
100
4
4000/4P
10
100
4
4000
10
100
4
5000
10
100
6
6300
10
100
6
Note: the specifications in the table is obtained as the ambient temperature of air circuit breaker is 40
℃
, with open installation; this is in
compliance with the specification of copper busbars adopted under the heating conditions regulated in IEC/EN60947-2.
8.
Recommendation for user's connecting bus-bar
NA1-1000
200
5
30
1
400
5
30
2
630
5
40
2
800
6
50
2
1000
8
50
2
Inm(A)
NA1-3200
NA1-4000
NA1-6300
In(A)
3200
737
307
4000/3P
921
-
4000/4P
900
-
4000
575
-
5000
898
-
6300
1426
-
NA1-2000
630
70
34.4
800
110
50
1000
172
78
1250
268
122
1600
440
200
2000
530
262
2000
384
200
2500
600
312
9. Power loss
Drawer type
Fixed type
Power
loss (W)
NA1-1000
200
40
33
400
101
85
630
123
107
800
110
94
1000
177
476
Making the secondary circuit power, the motor-driven mechanism can
store energy automatically until hearing the click and energy stored
"
indicating on the panel. Otherwise press the storage handle for 6
times until hearing the click and the indicator display energy stored”
And the closing operation can be realized either by closing
electromagnet or manual button.
11. Temperature compensation correction
Standard
IEC/EN60947-2
40
℃
45
℃
50
℃
55
℃
60
℃
65
℃
Ambient
temperature
NA1-2000
630
630
630
630
610
610
800
800
800
800
800
800
1000
1000
1000
1000
1000
1000
1250
1250
1250
1200
1150
1150
1600
1600
1500
1500
1300
1300
2000
1900
1900
1800
1700
1650
2000
2000
2000
2000
2000
2000
NA1-1000
200
195
192
182
174
163
400
395
384
328
248
192
630
623
605
584
548
500
800
790
768
725
696
620
1000
985
960
924
870
810
NA1-3200
NA1-4000
NA1-6300
2500
2400
2300
2200
2200
2200
3200
3000
3000
2800
2800
2600
4000
3800
3600
3400
3200
3200
4000
4000
4000
4000
4000
4000
5000
5000
5000
4800
4800
4800
6300
6000
5600
5400
5200
5100
40
65
60
45
70
55
50
Ambient temperature
(℃)
1800
2000
2200
2400
2600
2800
3000
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
R
a
te
d
c
u
rr
e
n
t
(
A
)
In=4000A
In=3200A
In=2500A
In=2000A
NA1-3200, NA1-4000
40
65
60
45
70
55
50
Ambient temperature
(℃)
3800
4000
4200
4400
4600
4800
5000
5200
5400
5600
5800
6000
6200
6400
6600
6800
7000
R
a
te
d
c
u
rr
e
n
t
(
A
)
In=6300A
In=5000A
In=4000A
NA1-6300
40
65
60
45
70
55
50
Ambient temperature
(℃)
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
R
a
te
d
c
u
rr
e
n
t
(
A
)
In=2000A
In=1600A
In=1250A
In=1000A
In=800A
In=630A
NA1-2000
45
40
50
55
60
65
0
200
400
600
800
1000
1200
Ambient temperature
(℃)
NA1-1000
R
a
te
d
c
u
rr
e
n
t
(
A
)
In=1000A
In=800A
In=630A
In=400A
In=200A
Note: The ACB is to calibrated at 40
℃
, special application please refer to the table above.