Copyright CPS America Co., Ltd. Page 33
G. DC Protection
This is the over current and over voltage protection that is used for the
Direct Current (DC) side. Please refer to configuration diagram that shown
in Appendix I to connect have a proper configuration for the DC side of PV
system.
The PV Inverter is shipped with dummy fuses (solid aluminum cylinders in the
shape of the proper fuses). Since there are four pairs of DC input ports, four
fuse holders shall be equipped for the four positive (+) polarity ports and
others fuse holders are equipped for the four negative (-) polarity ports.
Therefore, there are supports to have eight fuse folders, total, to the DC-side
as shown in figure 6.2.5:
Figure 6.2.5: Location of DC Fuses Holders
IMPORTANT
The PV Inverter is shipped with a dummy fuse in the fuse holder.
It is necessary to select the proper series fuse depending with the
solar modules that are used. Remove all dummy fuses prior to
installation and operation.
The installer or qualified service personnel should select the required DC
fuses during the installing procedure. The rating selection of the DC
protection fuses should be selected based on the amount of solar modules
connected in the PV system.