No.
Name
Range/meaning
Default
Status
00
Power down auto restart
0: no restart : 1: restart
1
check/set
01
DHW water temp. return differential
2~15
℃
,
minus differential
2
℃
check/set
02
Air conditioning return differential
2~15
℃
,
minus differential
2
℃
check/set
03
Copper pipe temp to start defrost
-20~5
℃
0°C
check/set
06
Defrost stop temp
10~35
℃
30
℃
check/set
07
Max defrost duration time
15~99 mins
15
check/set
08
Defrost interval time between 2 defrosts
15~99 mins
35
check/set
09
Air temp to start DHW electrical heater
-20~20
℃
0
℃
check/set
10
Air temp. to start AC electrical heater
-20~20
℃
0°C
check/set
11
Reserved
check/set
12
Compressor discharge air protection temp
A0 ~ C7 = (212°F~260°F)
B0
check/set
13
Defrost interval time multiply rate
0: no defrost 1~4: parameter 08*1~4
1
check/set
14
Function parameter
0: G3 is seasonal switch valve:
0
check/set
1: G3 is solar pre-heat valve:
26
AC water pump running mode
0, 1, 2
0: don’t stop
1: stops when it reaches target temp
2: run 1 minute every 15 minutes then
stops
0
check/set
27
2
nd
heat source control validation
0, 1 (0: 2
nd
heat source control
0
check/set
disable; 1: control enable)
28
Air temp to start 2nd heat source control
-15~10
℃
-15
℃
check/set
NOTE:
1.
Press the
key for 5 seconds, you will hear a beep. The factory default parameters
will be reset.
Usage of Parameter 26: AC water pump working modes.
If you are NOT using an AC buffer tank, the Parameter 26 is set to 0. The AC water
pump will work continuously to keep the AC loop water temperature always the same.
If you are using an AC buffer tank, the parameter 26 will be set to 1.
Summary of Contents for CX45
Page 4: ...4...
Page 9: ...9 Freeze protection...
Page 10: ...10...
Page 11: ...11...
Page 12: ...12...
Page 13: ...13...
Page 14: ...14...
Page 15: ...15...
Page 16: ...16...
Page 17: ...17...
Page 18: ...18...
Page 19: ...19...
Page 20: ...20...
Page 21: ...21...
Page 22: ...22...
Page 23: ...23...
Page 24: ...24...
Page 33: ...33 Clearances unit mm 200mm 8 350mm 14 400 16 500 20 1000 40...
Page 39: ...39 G3 VALVE Seasonal Switch Valve Solar Pre heat Valve...
Page 40: ...40 G1 Valve DHW and AC...