13. Troubleshooting table 
 
 

Fault Cause 

Remedy

 

 

The appliance does not operate 

There is no power supply 

Check the power supply

 

 
The appliance does not start 

The regulator does not start the appliance 

Check the functioning of the regulator

 

 
Room temperature is high 

The appliance does not operate 

Detect the cause of not starting

 

 

Wrong setting values 

Change the setting values 

 

Air volume too low 

Check the filters 

 

The compressor does not start 

See the item ‘compressor does not operate’

 

 

The automatics does not function 

Check the regulating equipment 

 

The load exceeds the nominal load 

Accept the small rise in heat 

 
Room temperature is low 

Wrong setting value 

Change the setting value

 

 

The regulator does not function 

Check the regulator and the sensors 

 
Low air volume 

No power supply 

Check the power supply

 

 

The filter is clogged 

Clean the filter 

 

The thermal protection of the fan is  
switched on 

Switch off the thermal protection, detect the 

 cause 

 
High pressure switch switches on  The control of the condensation  

pressure does not function 

Check the control of the condensation pressure

 

 

The fan of the condenser has stopped 

Detect the cause of stopping 

 

The high pressure switch is set incorrectly 

Replace the switch 

 
Low pressure switch switches on  The low pressure switch is set incorrectly 

Replace the switch

 

 

The condensation pressure is too low 

Increase the setting of the regulator 

 

The battery is frozen 

Defrost the appliance, check the freezing protection 

  

board

 

 

The filter of the evaporator is clogged 

Clean the filter 

 
The compressor does not operate  The fuse has switched on 

Check the fuse and detect the cause

 

 

The thermal protection has switched on 

Check the thermal protection and detect the cause 

 

The contactor does not function 

Replace the contactor 

 

The compressor does not receive a starting  
command Check 

the 

automatics 

 
The free cooling does not function  The damper motor does not operate 

Repair or replace the damper motor

 

 

Wrong setting values in the regulator 

Change the setting values 

 

The control system does not function 

Repair the control system 

 
The damper motor remains open  The damper motor is damaged 

Repair or replace the damper motor

 

Summary of Contents for IT 500 Series

Page 1: ...ns Operating Instructions Maintenance Instructions Read this manual carefully before installing and operating the appliance Chiller Oy assumes no legal responsibility for any damages resulting from in...

Page 2: ...of the appliance 7 Setting values of the sensors and safety devices 8 Installation of the appliance 9 Connecting the appliance to the power supply 10 Activating the appliance 11 Connection data of the...

Page 3: ...pliance in a dry and preferably warm room Make sure the delivery contains all accessories indicated in the documents Any shipping damages on the appliance are to be reported to the shipping company wi...

Page 4: ...ir EU4 EU4 Cooling agent standard supply R407C R407C Length L mm 1 620 1 620 Width B mm 800 800 Height H mm 450 450 Grille width BC 900 900 Grille height HC 550 550 Installation hole dimensions B H mm...

Page 5: ...awings A ELECTRICAL BOARD F CONDENSER FAN B SERVICE DOOR FOR THE FAN G SERVICE DOOR FOR THE CONDENSER C SERVICE DOOR FOR THE COMPRESSOR H EXHAUST AIR GRILLE D FREE COOLING WITH INTAKE AIR I FREE COOLI...

Page 6: ...axle Outside temperature exceeding the setting value of the sensor TE3 the fan P1 is not allowed to operate When the temperature in the intake air duct falls below the setting value of sensor TE2 the...

Page 7: ...en a breakdown occurs the relay D1 deactivates the compressor When the indoor temperature exceeds its setting value the free cooling fan P1 is activated and the damper controlling the free cooling is...

Page 8: ...8 Sensor TE3 Fan P1 Fan P2 Fan P3 Motorized damper M...

Page 9: ...9 High pressure switch Compressor Low pressure switch Grille...

Page 10: ...10 7 Setting Values of the Sensors and Safety Devices Appliance Setting value C TE1 25 TE2 12 TE3 18 Appliance Setting value bar LPS 2 3 5 HPS 17 5 24 LPS low pressure switch HPS high pressure switch...

Page 11: ...nstall the appliance above electronic devices or furniture as condense water may accidentally drip from the appliance Make sure the condense pipe allows the water a free flow out of the appliance The...

Page 12: ...threat fasten the l formed sheet metal strips between the appliance and the wall The metal sheets are fastened with 7 mm self tapping screws Supporting of the appliance requires special attention in c...

Page 13: ...13 Fastening with a locking nut A NUT B WASHER C TWIN NUT...

Page 14: ...installation perform the following checks before starting the appliance The appliance has been installed in horizontal position on the proper point of installation The appliance is provided with the...

Page 15: ...he grille and replace it with a new one Wash the old filter in order to get an exchange filter There is an intake air filter at the end of the appliance Remove the filter and replace it with a new one...

Page 16: ...ressor 230 1 50 1 34 6 6 Evaporator fan 230 1 50 0 043 0 2 Condenser fan 230 1 50 0 35 2 8 Free cooling fan 230 1 50 0 09 0 9 IT560 Component Voltage Connection capacity kW Operating current A Compres...

Page 17: ...The control of the condensation pressure does not function Check the control of the condensation pressure The fan of the condenser has stopped Detect the cause of stopping The high pressure switch is...

Page 18: ...04300 Tuusula Finland Declares under its sole responsibility that the construction of the units IT540 IT560 To which this declaration relates is in conformity with the following directives 98 37 EEC...

Page 19: ...fan 1 CH200F Freezing protection board 1 CH300I Control board 1 MOT100I Damper motor 1 FLR001F Evaporator filter 1 FLR100I Free cooling horizontal filter 1 FLR200F Free cooling bag filter 1 GRL003F I...

Page 20: ...0F Freezing protection board 1 CH300I Control board 1 MOT100I Damper motor 1 FLR001F Evaporator filter 1 FLR100I Free cooling horizontal filter 1 FLR200F Free cooling bag filter 1 GRL003F Intake grill...

Page 21: ...ntre of the fan and pull the fan straight downwards Be careful as the fan may be tightly fixed Loosen the screws in the corners of the motor stand The motor is fastened by the rear side of the motor s...

Reviews: