Fig. 7 the wire controller
Fig.8 the indoor PCB
Malfunction code
:
P2
(
the outdoor unit transducer module protection faulty
)
Turn off the power
1、whether the compressor’s connecting wiring is loose
2、check whether the module and radiator are firm
N
1、pls make the compressor’s
connecting wiring firm。
2 、 pls fixup the IPM and
radiator together
Y
Check whether the compressor’s winding value is normal
(
refer to SNYO C-6RZ146H1A winding value:T-R 0.452
Ω
T-S0.452
Ω
R-S0.452
Ω)
N
The compressor is bad, then
change it.
The intelligent power module is bad , and
then change it.
Y
The faulty cause
:
1 、 the compressor’s connecting wiring is
loose;
2、the IPM module and radiator are not firm
3、the IPM board has the fault.
4、the compressor is bad.
The dynatron Q3 reference value:
be pole :The positive pole resistance
:
660
Ω
the negative pole resistance
:
961
Ω;
bc pole :The positive pole resistance
:
659
Ω
the negative pole resistance :1439
Ω
The clamping diode’s parameter:
VD15 The positive pole resistance
:
389
Ω
the
negative pole resistance
:
392
Ω
VD16 The positive pole resistance
:
497
Ω
the
negative pole resistance
:
1012
Ω
Summary of Contents for CMV-50V9A-S
Page 1: ...DC Inverter Split Air Condition Unit SERVICE MANUAL ...
Page 6: ......
Page 8: ...The compressor s condensing pressure graph ...
Page 12: ...Capacity Correction Factor Due to Tubing Length One Way Cooling Heating ...
Page 13: ...Pressure Curve Suction Pressure Curve Discharge Pressure Curve ...
Page 18: ...5 The outdoor unit structure exploded view 5 1 The structure exploded view for CMV 50V9A S ...
Page 19: ......
Page 20: ...5 2 The structure exploded view for CMV V64T9AD ...
Page 21: ......