![Chigo CCA-18CR1 Technical Manual Download Page 74](http://html1.mh-extra.com/html/chigo/cca-18cr1/cca-18cr1_technical-manual_2601239074.webp)
R410A50Hz Universal Outdoor Series Technical Manual Duct Type Indoor Unit
71
GD Chigo Heating & Ventilation Equipment Co., Ltd.
6.8 CTH-48HR1,CTH-48CR1
MODEL
CTH-48HR1
COOLING
OUTDOOR TEMPERATURE DRY
Indoor Conditions
21ºC
25ºC
30ºC
35ºC
40ºC
43ºC
21ºC D 15ºC W
Total capacity kW
13.15
13.02
12.89
12.70
11.40
9.69
Input kW.
4.93
5.03
5.29
5.29
5.61
5.84
24ºC D 17ºC W
Total capacity kW
13.81
13.67
13.54
13.34
11.97
10.17
Input kW.
5.03
5.13
5.24
5.39
5.72
5.96
27ºC D 19ºC W
Total capacity kW
14.50
14.35
14.21
14.00
12.57
10.68
Input kW.
5.13
5.24
5.34
5.50
5.84
6.07
29ºC D 19ºC W
Total capacity kW
15.08
14.93
14.78
14.56
13.09
11.10
Input kW.
5.24
5.34
5.45
5.61
5.96
6.19
32ºC D 23ºC W
Total capacity kW
15.68
15.52
15.37
15.15
13.60
11.55
Input kW.
5.34
5.45
5.55
5.72
6.07
6.32
6.9 CTH-60HR1,CTH-60CR1
MODEL
CTH-60HR1
COOLING
OUTDOOR TEMPERATURE DRY
Indoor Conditions
21ºC
25ºC
30ºC
35ºC
40ºC
43ºC
21ºC D 15ºC W
Total capacity kW
15.03
14.88
14.73
14.51
13.03
11.07
Input kW.
5.55
5.67
5.96
5.96
6.32
6.58
24ºC D 17ºC W
Total capacity kW
15.78
15.62
15.47
15.24
13.68
11.62
Input kW.
5.67
5.78
5.90
6.08
6.45
6.71
27ºC D 19ºC W
Total capacity kW
16.57
16.40
16.24
16.00
14.36
12.20
Input kW.
5.78
5.90
6.02
6.20
6.58
6.85
29ºC D 19ºC W
Total capacity kW
17.23
17.06
16.89
16.64
14.96
12.69
Input kW.
5.90
6.02
6.14
6.32
6.71
6.98
32ºC D 23ºC W
Total capacity kW
17.92
17.74
17.57
17.31
15.54
13.20
Input kW.
6.02
6.14
6.26
6.45
6.85
7.12