11. The Specification of Wiring
Model
12kBtu/h
18kBtu/h
24kBtu/h
36kBtu/h
Indoor power supply
V/Ph/Hz
220~240/1/50
Outdoor power supply V/Ph/Hz
220~240/1/50
Connection
wiring
Outdoor Power
Supply
From
indoor unit
From
indoor unit
Power supply individually for
indoor and outdoor
Power
wiring
mm
2
3×1.5
3×2.5
3×2.5/3×1.0
3×4.0/3×1.0
Signal
wiring
mm
2
5×1.5
5×1.5
RS485 twisted shielded wire pair
2×0.5
Model
36kBtu/h
48kBtu/h
60kBtu/h
Indoor power supply
V/Ph/Hz
220~240/1/50
Outdoor power supply
V/Ph/Hz
380~415/3/50
Connection wiring
Outdoor Power Supply
Power supply individually for indoor and outdoor
Power
wiring
mm
2
5×1.5/3×1.0
5×1.5/3×1.0
5×2.5/3×1.0
Signal
wiring
mm
2
RS485 twisted shielded wire pair 2×0.5