Isolated Ground Receptacle

This product incorporates an isolated ground receptacle,
identified by the orange triangle on its face. This feature may be
useful to reduce common noise in the connected equipment. Its
intended use is to reduce electrical noise (electromagnetic
interference) by purposely insulating the grounding circuit from
any metallic wiring system. The ground pin of the receptacle is
connected to the green/yellow wire and is isolated from the
metal mounting yoke of the receptacle. The accessible metal of
the product is connected to the green wire. If it is not desired to
use this feature, connect the green/yellow and green wires
together.

References

Application Guide for Isolated Ground Wiring Devices 2007,
National Electrical Manufacturers Association (NEMA)

IEEE Std 1100

-2005, “IEEE Recommended Practice for

Powering and Grounding Electronic Equipment” (Emerald
Book), Section 8.5.3.2.

IEEE Std 142™-2007, “IEEE Recommended Practice for
Grounding of Industrial and Commercial Power Systems”
(Green Book), Sections 5.5.1, 5.5.2

NFPA-70, “National Electrical Code”, Article 250.146
Connecting Receptacle Grounding Terminal to Box.

(D) Isolated Ground Receptacles. Where installed
for the reduction of electrical noise (electromagnetic
interference) on the grounding circuit, a receptacle
in which the grounding terminal is purposefully
insulated from the receptacle mounting means shall
be permitted. The receptacle grounding terminal
shall be connected to an insulated equipment
grounding conductor run with the circuit conductors.
This equipment grounding conductor shall be
permitted to pass through one or more panel boards
without a connection to the panel board grounding
terminal bar as permitted in 408.40, Exception, so
as to terminate within the same building or structure
directly at an equipment grounding conductor
terminal of the applicable derived system or service.
Where installed in accordance with the provisions of
this section, this equipment grounding conductor
shall also be permitted to pass through boxes, wire
ways, or other enclosures without being connected
to such enclosures.

Informational Note: Use of an isolated equipment
grounding conductor does not relieve the
requirement for grounding the raceway system and
outlet box.

C22.2 No. 1, “Canadian Electrical Code, Part 1”, Rule 10-906
Bonding conductor connection to circuits and equipment.

(6) A bonding jumper shall be installed to connect
the bonding conductor to the grounding terminal of
a receptacle and in such a manner that
disconnection or removal of the receptacle will not
interfere with, or interrupt grounding continuity.

(7) In the case of metallically enclosed systems
where the grounding path is provided by the metal
enclosure, a bonding jumper shall be installed to
bond the grounding terminal of the receptacle to the
enclosure.

(8) Notwithstanding Sub-rules (6) and (7), the
bonding jumper, in the case of receptacles having
grounding terminals isolated from the mounting
strap required for special equipment, shall be

permitted to be extended directly back to the
distribution panel.

WARNING:

IMPROPER INSTALLATION CAN RESULT IN

DEATH OR SERIOUS PERSONAL INJURY! This mounting
system should be installed by qualified personnel.

IMPORTANT ! :

In addition to the CMS491/CMS491C/

CMS492/CMS492C installation instructions
accompanying the products, the following steps must
also be taken when installing the

CMS491P2,

CMS491CP2, CMS492P2,

and

 CMS492CP2.

The CMS491P2, CMS491CP2, CMS492P2, and CMS492CP2
must be connected to a 15 Amp branch circuit.

Installing EGX-SF2

1.

Loosen two Phillips head screws holding EGX-SF2 (A)
outlet box to outer housing. (See Figure 1)

2.

Rotate outlet box counter-clockwise until it is free to be
removed from housing. (See Figure 1)

3.

Remove outlet box from housing. (See Figure 1)

Figure 1

1

x 2

2

2

3

outlet box

housing

Summary of Contents for CMS491CP2

Page 1: ...491P2 CMS491CP2 CMS492P2 CMS492CP2 Powered Ceiling Storage Boxes Spanish Product Description German Product Description Portuguese Product Description Italian Product Description Dutch Product Description French Product Description CMS491P2 CMS492P2 CMS491CP2 CMS492CP2 ...

Page 2: ... WARRANTY It is the installer s responsibility to make sure all components are properly assembled and installed using the instructions provided READ ALL INSTRUCTIONS BEFORE USING THIS PRODUCT DANGER TO REDUCE THE RISK OF ELECTRIC SHOCK 1 Always turn off power at source before installing the outlet WARNING TO REDUCE THE RISK OF BURNS FIRE ELECTRIC SHOCK OR INJURY TO PERSONS Always turn off power at...

Page 3: ...Installation Instructions CMS491P2 CMS492P2 CMS491CP2 CMS492CP2 3 DIMENSIONS CMS491P2 DIMENSIONS INCHES MILLIMETERS CMS491CP2 ...

Page 4: ...CMS491P2 CMS492P2 CMS491CP2 CMS492CP2 Installation Instructions 4 DIMENSIONS continued DIMENSIONS INCHES MILLIMETERS CMS492P2 CMS492CP2 ...

Page 5: ...esapertar fixador Allentare il fissaggio Bevestiging losdraaien Desserrez les fixations Phillips Screwdriver Destornillador Phillips Kreuzschlitzschraubendreher Chave de fendas Phillips Cacciavite a stella Kruiskopschroevendraaier Tournevis à pointe cruciforme Adjust Ajustar Einstellen Ajustar Regolare Afstellen Ajuster A 1 EGX SF2 Power Conditioner Outlet B 1 Outlet cover Grounding screw installe...

Page 6: ...r structure directly at an equipment grounding conductor terminal of the applicable derived system or service Where installed in accordance with the provisions of this section this equipment grounding conductor shall also be permitted to pass through boxes wire ways or other enclosures without being connected to such enclosures Informational Note Use of an isolated equipment grounding conductor do...

Page 7: ...entical in size and insulation material and thickness to the grounded and ungrounded circuit supply conductors except that it is green with or without one or more yellow stripes is to be installed as part of the circuit that supplies the outlet Refer to Table 250 122 of the National Electrical Code regarding the appropriate size of the grounding conductor NOTE Pressure terminal or pressure splicin...

Page 8: ...ee Figure 3 OR See Figure 4 8 Tighten two Phillips screws to secure outlet box to EGX SF2 housing See Figure 3 OR See Figure 4 Figure 3 Figure 4 9 Make sure grounding screw is properly installed See Figure 5 WARNING ELECTRICAL SHOCK HAZARD Turn off power to device before performing service or connecting to outlet Figure 5 10 Remove 6 32 x 1 2 Phillips flat head screw and lock washer from front of ...

Page 9: ...from front of box See Figure 5 or See Figure 7 NOTE Make sure LED light on outlet box lines up with hole location on faceplate B See Figure 7 Figure 7 Outlet Box Use NOTE The PROTECTED light indicates that the surge protection circuitry is active and operational Figure 8 11 CMS491CP2 shown as example B housing box not shown for clarity lock washer LED light PROTECTED indicator light ...

Page 10: ...CMS491P2 CMS492P2 CMS491CP2 CMS492CP2 Installation Instructions 10 ...

Page 11: ...Installation Instructions CMS491P2 CMS492P2 CMS491CP2 CMS492CP2 11 ...

Page 12: ...4 6918 952 894 6918 Europe A Franklinstraat 14 6003 DK Weert Netherlands P 31 0 495 580 852 F 31 0 495 580 845 Asia Pacific A Office No 918 on 9 F Shatin Galleria 18 24 Shan Mei Street Fotan Shatin Hong Kong P 852 2145 4099 F 852 2145 4477 Chief a products division of Milestone AV Technologies 8800 002794 Rev00 2016 Milestone AV Technologies www chiefmfg com 03 16 ...

Reviews: