- 21 -
LOG list
The unit will keep an event log of the latest 30 events.
Events are:
–
shutdowns
–
service timer 1/2 reset
–
unit type changes
Together with each event, the running hours at the
time of the event will be stored.
Remote start operation
Installation wirings:
–
X25.1 & X25.2 to be wired for the remote start
switch.
–
X25.3 & X25.4 to be wired for the remote
contactor (open/close).
Fail classes
All the activated alarms of the Qc1002™ have their
own pre-defined fail class.
All alarms are enabled according to one of these three
statuses:
–
disabled alarm, no supervision of alarm (OFF)
–
enabled alarm, supervision of alarm all the time
(ON)
–
running alarm, only supervision when the
machine is running (RUN)
SERVICE TIMER
1
SERVICE TIMER
2
ENGINE ALARM
EMERGENCY
STOP
START FAILURE
STOP FAILURE
1
Controller type
2
Event number
3
Event
4
Running hours
Time: 00001h
EVENT LOG #04
Water
Qc1002
1
3
4
2
Summary of Contents for CPG 90-120 JD
Page 1: ...CPG 90 120 JD Instruction Manual for AC Generators English ...
Page 2: ......
Page 19: ... 19 This is the described menu flow for changing the unit type ...
Page 47: ... 47 Circuit diagrams ...
Page 48: ... 48 1310 3200 01 00 Applicable for CPG 90 120 John Deere Power circuit ...
Page 49: ... 49 ...
Page 51: ... 51 ...
Page 52: ... 52 1310 3200 00 00 Applicable for CPG 90 120 John Deere Engine circuit Qc1002TM ...
Page 53: ... 53 ...
Page 55: ... 55 ...
Page 56: ...Printed in Belgium 04 2010 1310 3012 23 www cp com ...