background image

18 

 

The analog input is setup to receive an externally powered 4-20 mA signal, but transmitters that require power to be 
supplied can be accommodated (contact factory for details).    

2.

 

The Analog input will need to be scaled to match the scaling of the flow transmitter’s output scaling.  

This is done 

under the Flow Input’s Options menu (see HydroACT menu for more information). After scaling the Flow Input, a 

calibration MUST be performed for the input to begin reading accurately.   

3.

 

Go into the PID Options menu and access the IWP setup screen discussed on page 15.   Change the Minimum setting 
to -100.00%.  Note: It is very important to have the negative sign (-) so it shows -100.00%.  Make sure the Maximum 
setting is set for +100%.  The IWP values must remain at -100% and +100% when flow pacing is being utilized. 

4.

 

Go into the PID Options menu and access the Flow Setup menu.  Change the Enabled setting from No to Yes.  Ensure 
the Flow Sensor 

setting is mapped to the Flow Input and the parameter shows “Flow”.  

 

5.

 

Next, set the 

Nominal Flow to match the plant’s 

typical flow rate.  For example, the plant may typically run at 400 

MGD and occasionally go up to 800 MGD and sometimes as low as 200 MGD.   Since 400 MGD is the typical flow rate 
the plant runs at, 400 should be entered as the Nominal Flow.    

6.

 

The next step is to change the High and Low Output settings for upper and lower controller output range (or pump 

speed) that you need at that “typical” flow rate.  In our example, when the plant is flowing at the typical flow rate of 

400 MGD it was determined from past experience that the lowest coagulant pump speed needed at that flow was 
10% (low NTU conditions) and the highest  pump speed needed would be 40% (high  NTU conditions).   Using this 
example, the customer would enter 40% for the High Output and 10% for the Low Output.   Using these settings the 
controller establishes an upper and lower control range for the SCM PID output for all flow rate conditions as shown 
in the below graph.  These settings allow the controller to make proportional changes to the dosage as flow changes 
and it will also limit the pump output to the appropriate min and max range (as defined by the blue lines in the below 
graph), further reducing the potential for excessive over or under feed of coagulant should a problem occur with the 
Streaming Current sensor.   

7.

 

If at any time the Streaming Current reading is not able to reach the Setpoint value, it may be due to needing to 
increase the High Output setting or decreasing the Low Output setting, or needing to increase or decrease the output 
limits discussed on page 12.  
 

 

 

Summary of Contents for DuraTrac 4

Page 1: ...Quick Startup Guide HydroACT Analyzer with DuraTrac 4 Streaming Current Sensor Version 11 10 16...

Page 2: ...Signal Wiring 6 Output Signal and Scaling Information 6 Gain Adjustment Including Cleaning Procedure 7 Sensor Cleaning Frequency 7 Find the Optimum Streaming Current Value and How to Zero the Reading...

Page 3: ...c drain near the sensor as shown below is advised when possible This allows for quick visual verification of flow and reduces sensor maintenance i e seal replacements There are two 1 FNPT sample ports...

Page 4: ...4 Dimensions Mounting DuraTrac 4 Sensor HydroACT...

Page 5: ...the alarm and silence the beeping Menu Navigation The HydroACT Interface is navigated using the buttons located below the display From the Home Screen press the Menu button to access the Menu Screen s...

Page 6: ...Options Connections Output Signal and Scaling Information The Streaming Current 4 20 mA Output is typically mapped to Analog Output 1 8 and scaled 500 to 500 The Signal Health 4 20 mA Output is typica...

Page 7: ...de the probe block or on the probe piston surfaces Try cleaning again and be sure to use the cleaning agent on all surfaces Once reading appears to have stabilized add more raw water until the reading...

Page 8: ...sufficient time to stabilize 2 hours recommended for brand new unit the below procedure should be followed to find the optimum SCV that will be used as the setpoint by which to gauge coagulant dosing...

Page 9: ...the Streaming Current waveform signal go to Menu SCM Options Diagnostics Waveform The waveform view will update every 5 seconds The waveform display can aid tremendously with troubleshooting problems...

Page 10: ...ngly Holding down the Select button will cause the output to change more rapidly Home Screen To make faster changes to the pump speed or to change the setpoint value if not using Zero Offfset simply h...

Page 11: ...art Delay 00 00 00 If 0 controller will initialize in the Start Mode see below for user defined time HH MM SS before switching to Run Mode This occurs on power up and when Process Signal input receive...

Page 12: ...to increase the rate of PID adjustments Options Setup Output Setup Parameter Factory Setting Notes Manual Value 0 Allows the user to adjust the pump output when the Run Mode is set to Manual This sett...

Page 13: ...ero at all times Ramping Disabled Ramping feature is generally only used for applications that start and stop automatically PID control can struggle during a startup event to bring the process variabl...

Page 14: ...al value is increased and vice versa Typical settings used are 0 200 to 1 000 This setting determines the controller s proportional response to the difference between the Setpoint and Process Variable...

Page 15: ...is highly sensitive to noise in the process variable signal and relies on the PV to be fairly proportional to the PID output changes which the Streaming Current reading is generally not If used the Up...

Page 16: ...afe on PV Alarm Disabled Enabling this feature will cause the PID to revert to the Failsafe Mode in response to a Streaming Current alarm high or low reading going active If the Failsafe Mode is set f...

Page 17: ...ns Setup PID Flow Setup Parameter Factory Setting Notes Enabled Disabled This setting is disabled on all units leaving the factory even those ordered with flow pacing capability Enable this setting to...

Page 18: ...is the typical flow rate the plant runs at 400 should be entered as the Nominal Flow 6 The next step is to change the High and Low Output settings for upper and lower controller output range or pump s...

Reviews: