background image

15 

 

Value) + Last Integral Output value.  The minimum and maximum Integral 
output is determined by the settings under Integral Windup Protection. 

 

 

This setting is generally not useful to SCM PID control and should be left 
for zero.  Customers not experienced with PID tuning are highly 
recommended to leave Derivative at 0.000 as it is rarely needed and is 
more apt to cause difficulties in tuning the PID.  The derivative 
component causes the output to change in response to changes in the 
process variable (e.g. backing down the PID output if the reading moves 
towards the setpoint).  The derivative response is proportional to the rate 
of change of the PV as seen between two consecutive PV updates.   If the 
rate of change goes to zero (i.e. stable process variable), then the 
Derivative output also goes to zero. Increasing the derivative setting will 
cause the control system to react more strongly to changes in the PV. 
Most practical control systems use a very small or no derivative setting.  
This is because the Derivative Response is highly sensitive to noise in the 
process variable signal and relies on the PV to be fairly proportional to 
the PID output changes, which the Streaming Current reading is generally 
not.   If used, the Update Delay time should be set closer to the process 
lag time (which is the time needed for the analyzer to respond to a 
change in chemical dosage).  

Update Delay: 

00:00:02 

The Update Delay setting determines the frequency by which the Integral 
Output value is calculated.    Increasing this time (e.g. going from 2 to 5 
seconds) will slow down the PID output adjustments, and vice versa.     

 

Options>Setup>PID Setup (To access the IWP tab, press the far right Function button,  which is the button just 
below the Right Arrow shown at the bottom of the display) 

 

Parameter 

Factory Setting 

Notes 

Enabled: 

Yes 

Leave this set for Yes.  

Minimum: 

0% 

If the Flow pacing feature is disabled, this must be set to match the 
Minimum Output Limit (discussed on page 12). When the Flow pacing 
feature is enabled, this must be set for -100% (note: negative 100).     

Maximum: 

100% 

If the Flow pacing feature is disabled, this must be set to match the 
Maximum Output Limit (discussed on page 12). When the Flow pacing 
feature is enabled, this must be set for +100% (note: positive 100).     

 

 

 

Summary of Contents for DuraTrac 4

Page 1: ...Quick Startup Guide HydroACT Analyzer with DuraTrac 4 Streaming Current Sensor Version 11 10 16...

Page 2: ...Signal Wiring 6 Output Signal and Scaling Information 6 Gain Adjustment Including Cleaning Procedure 7 Sensor Cleaning Frequency 7 Find the Optimum Streaming Current Value and How to Zero the Reading...

Page 3: ...c drain near the sensor as shown below is advised when possible This allows for quick visual verification of flow and reduces sensor maintenance i e seal replacements There are two 1 FNPT sample ports...

Page 4: ...4 Dimensions Mounting DuraTrac 4 Sensor HydroACT...

Page 5: ...the alarm and silence the beeping Menu Navigation The HydroACT Interface is navigated using the buttons located below the display From the Home Screen press the Menu button to access the Menu Screen s...

Page 6: ...Options Connections Output Signal and Scaling Information The Streaming Current 4 20 mA Output is typically mapped to Analog Output 1 8 and scaled 500 to 500 The Signal Health 4 20 mA Output is typica...

Page 7: ...de the probe block or on the probe piston surfaces Try cleaning again and be sure to use the cleaning agent on all surfaces Once reading appears to have stabilized add more raw water until the reading...

Page 8: ...sufficient time to stabilize 2 hours recommended for brand new unit the below procedure should be followed to find the optimum SCV that will be used as the setpoint by which to gauge coagulant dosing...

Page 9: ...the Streaming Current waveform signal go to Menu SCM Options Diagnostics Waveform The waveform view will update every 5 seconds The waveform display can aid tremendously with troubleshooting problems...

Page 10: ...ngly Holding down the Select button will cause the output to change more rapidly Home Screen To make faster changes to the pump speed or to change the setpoint value if not using Zero Offfset simply h...

Page 11: ...art Delay 00 00 00 If 0 controller will initialize in the Start Mode see below for user defined time HH MM SS before switching to Run Mode This occurs on power up and when Process Signal input receive...

Page 12: ...to increase the rate of PID adjustments Options Setup Output Setup Parameter Factory Setting Notes Manual Value 0 Allows the user to adjust the pump output when the Run Mode is set to Manual This sett...

Page 13: ...ero at all times Ramping Disabled Ramping feature is generally only used for applications that start and stop automatically PID control can struggle during a startup event to bring the process variabl...

Page 14: ...al value is increased and vice versa Typical settings used are 0 200 to 1 000 This setting determines the controller s proportional response to the difference between the Setpoint and Process Variable...

Page 15: ...is highly sensitive to noise in the process variable signal and relies on the PV to be fairly proportional to the PID output changes which the Streaming Current reading is generally not If used the Up...

Page 16: ...afe on PV Alarm Disabled Enabling this feature will cause the PID to revert to the Failsafe Mode in response to a Streaming Current alarm high or low reading going active If the Failsafe Mode is set f...

Page 17: ...ns Setup PID Flow Setup Parameter Factory Setting Notes Enabled Disabled This setting is disabled on all units leaving the factory even those ordered with flow pacing capability Enable this setting to...

Page 18: ...is the typical flow rate the plant runs at 400 should be entered as the Nominal Flow 6 The next step is to change the High and Low Output settings for upper and lower controller output range or pump s...

Reviews: