1.4 GENERAL FL
UE R
EQUIR
EMENT
S
CHEMINÉES
PHILIPPE
RADIANTE 747 2V PR
07
*Please keep these instructions for future reference.
»
Only an approved
Cheminées Philippe
flue kit should be installed with this fireplace
»
Mixing flue system components and/or modifying the dimensional specification of the flue and cowl is
NOT recommended, unless approved by
Cheminées Philippe Australia
»
A
minimum 4.5 metres
of flue is required from the top of the fireplace gather to the cowl
»
A minimum 50mm clearance around the triple skin flue is to be maintained from the outer casing to any
combustible surface
»
A minimum 920mm clearance is to be maintained around the single skin flue to any combustible surface
»
Do
NOT
install bends directly on top of the fireplace gather. A minimum 900mm length of flue must be
installed first before the first bend is positioned
»
No more than 2 x 45 degree bends are allowed
»
90 degree bends are
NOT
to be used
*All dimensions in mm
FLUE SYSTEM
FLUE BENDS
MINIMUM EXTERNAL FLUE HEIGHTS & COWL CLEARANCES - AS PER AS/NZS 2918:2018