INBUIL
T CA
VITY DIMENSIONS 4.3
22
CHEMINÉES
PHILIPPE
RADIANTE 747 2V PR
PLAN VIEW
SIDE VIEW
ENCLOSURE MATERIALS & CLEARANCES:
Brick/hebel Enclosure*:
Use a minimum
110mm solid brick or hebel with a minimum
clearance of 100mm to the back of the unit
and 200mm on either side.
Skamotec Enclosure**:
Use a minimum
50mm Skamotec board with 50mm air
gap behind (using Skamotec battens),
with a minimum 200mm clearance to the
back of the unit and 200mm on either
side. Ventilation is not required behind the
Skamotec board in this case as the vents
will be on the fireplace cavity
AIR INLET AND OUTLET GRILLES:
Intake Size:
A minimum surface area of
360cm2 is required for air intake on either
side of the bottom of the cavity, (minimum
size grilles 9cm x 40cm) and should be in
line with the base of the fireplace.
Outtake Size:
The same size on either
side is required for the top air outtake on
either side OR one long outtake grill can be
installed at the front of the cavity (directly
below the internal deflector plate)creating a
minimum of 720cm2 in total size (minimum
size vent 9cm x 80cm)
EXISTING MASONRY CHIMNEY:
When 200mm side clearance can’t be
achieved then it is recommended to use
custom metal vent attachments that are
fixed to either side of the unit to assist with
adequate air flow. In this case, a minimum
100mm air gap on the back and sides is
recommended
All dimensions are in millimetres
Deflector & rockwool minimum 500mm
below the ceiling
815
Unit
Cavity opening
810
731**
631*
1510
50
50
560
50
*Refer
to pages
8 & 21
***All specifications are for both FD (left) or FG (right) glass sided models