background image

Page 2 

2.  User Command Protocol. 

2.1  Command Packet. 

The  command  protocol  is  based  around  a  simple  delimited  control  packet,  allowing  easy 
identification of command start and end.  The packet includes a block parity byte increasing the 
robustness of transmission; the packet format is shown in Figure 2.1. 
 
 

>

 

(ASCII 62)

 

Command 

Parameter 

Parity 

<

 

(ASCII 60)

 

 

Figure 2.1  Command Frame Format. 

 
The  command  byte  values  are  defined  in  the  following  section,  and  may  or  may  not  require  a 
parameter byte, for example data rate.  The parity byte is an even block parity of all bytes (other 
than itself), including the delimiters.  Calculation for parity bit 

n

 is therefore the sum of each bit 

n

 

using modulo 2 arithmetic. 
 
For a command not requiring a parameter, an arbitrary dummy byte should be used.  This can be 
any  value  as  the  number  is  not  processed  other  than  in  determining  the  parity  of the command 
packet. 
 
Example. 
The command set includes a test command (

for use from RS232 only

), value 37 (ASCII "%").  The 

response to the command is to echo back the string "

Test command rxd ok n

", where n is the 

value of the parameter byte.  This may be checked from a terminal program by typing : 
 
>%dC< 

ie byte values 62, 37, 100, 67, 60 

 
The parameter value is set at 100, so the parity byte is 62 

 37 

 100 

 60 = 67. 

The microDAQ should reply with 

"Test command rxd ok 100" 

 

2.2  Acknowledgement. 

A  command  packet  is  positively  acknowledged  if  it  is  correctly  formatted  and  the  parity  byte  is 
correct.  A positive acknowledgement is denoted by the transmission of ASCII 42 ('*'), a negative 
acknowledge indicating an invalid command by ASCII 33 ('!').  Recognised command values are 
then acted upon, though unrecognised values are discarded. 
 

2.3  User Commands. 

The available user command set is summarised in Figure 2.2. 
 

Command       

(* DTC only) 

Byte, 

Char/

ASCII 

Parameter 

Description 

Standby 

S/83 

None 

Set all data streaming off. 

Reset 

R/82 

None 

Request a soft device reset - microDAQ is reinitialised. 

Rezero 

Z/90 

None 

Request  a  rezero,  the  number  of  samples  as  set  in 
microDAQSetup. 

Derange * 

D/68 

None 

Calibration  is  rebuilt  with  the  appropriate  deranging  factor 
applied,  the  DTC  scanner  deranging  gain  is  switched  into 
circuit. 

Summary of Contents for microDAQ

Page 1: ...Folgate Road North Walsham Norfolk NR28 0AJ ENGLAND Tel 01692 500555 Fax 01692 500088 microDAQ Pressure Scanner Acquisition System USER PROGRAMMING GUIDE e mail info chell co uk Visit the Chell websit...

Page 2: ...ified in this manual may impair the user s protection Chell Document No 900167 Issue 1 3 ECO 1270 Date 28th November 2014 Chell s policy of continuously updating and improving products means that this...

Page 3: ...ol 7 4 1 4 Control Via RS232 7 4 1 5 Data Rate 7 4 2 TCP 8 4 2 1 Overview 8 4 2 2 Connection 8 4 2 3 TCP Protocol 8 4 2 4 TCP Data Rate 8 4 2 5 Control Via TCP 9 4 3 CAN 9 4 3 1 Overview 9 4 3 2 CAN B...

Page 4: ...received command may be acknowledged if required The following sets out the essentials of the command protocol the data packet format for all channels in addition to the message identifier arrangemen...

Page 5: ...ASCII The response to the command is to echo back the string Test command rxd ok n where n is the value of the parameter byte This may be checked from a terminal program by typing dC ie byte values 6...

Page 6: ...pressure value is averaged over the time between data delivery cycles Rezero and Rebuild G 71 None Requests a rezero followed by a calibration table rebuild with the calculated zero offsets being app...

Page 7: ...rnal RAM Disable the data delivery for the chosen channel Get Status 63 0 Short 1 With temp 2 Full 3 Pressure reading 4 Temp readings 5 Excitation reading 6 Hall sensor read 7 Firmware ID 8 Unit seria...

Page 8: ...channels A calibration table rebuild is then performed Hardware Trigger T 84 byte 0xab a 0 Disable a 1 Enable b 0 RS232 b 1 TCP b 2 CAN b 3 Internal RAM b 4 Internal RAM stop on full Enables or disabl...

Page 9: ...in ascending order as comma delimited ASCII engineering units ie degrees C The full status data contains the above followed by fields for the setup options of the microDAQ Each field is comma delimite...

Page 10: ...ations bandwidth as well as less processor overhead within the microDAQ it is recommended that engineering unit conversions be applied at the client Protocol Example data format Note 16 bit LE 0x00 0x...

Page 11: ...ing to 10kHz from the default maximum 20kHz due to internal issues regarding string handling The 16 bit little ended protocol is most efficient from the microDAQ s viewpoint the data being calibrated...

Page 12: ...account to avoid losing data Please note that if streaming at high data rates it is essential that a good network infrastructure is used It is recommended that any streaming is performed over a priva...

Page 13: ...ty to avoid overlap of message identifiers in a multiple microDAQ installation Data are two bytes unsigned scaled to full scale ie 0x0000 might represent 5psi 0xffff 5psi The data are user selectable...

Page 14: ...MSB CH18 MSB CH22 MSB CH26 MSB CH30 MSB 2 CH2 LSB CH6 LSB CH10 LSB CH14 LSB CH18 LSB CH22 LSB CH26 LSB CH30 LSB 1 CH1 MSB CH5 MSB CH9 MSB CH13 MSB CH17 MSB CH21 MSB CH25 MSB CH29 MSB 0 Ch1 LSB Ch5 LSB...

Page 15: ...The offset from the base identifier may be selected as being 0x10 0x20 0x30 0x40 or 0x50 For example the base data message identifier of 0x220 might be set up to receive commands over CAN on message...

Page 16: ...on the selected CAN message type single message or multiple message IDs as detailed in section 4 3 3 above In addition to the above an internal RAM dump sends a 9 or 6 byte header which is sent as soo...

Page 17: ...ion of the standard command set and can be transmitted all through the same comms connection These commands change the valves accordingly to perform a zero function or a purge function and also to sim...

Reviews: