2.0 C-Linx PROGRAMMING OPTIONS
Cheetah Xi Programming Manual
2-19
P/N: 06-651
Rev 1, 09/2013
Exhibit 2-18: Programming Features Cont.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
Defaults
(FAAST
Detector)
Common
Loop Number of Device
Y
1 - 4
1
Address of Device
Y
1 – 254
Custom Message
Y
60 character user defined
(1-001 FAAST DETECT
Loop 1 - Address 001)
Y
Default/
User Defined
Zone Assignments
Y
1
– 253
2
Predischarge Type
Y
Alarm Only Device
/ 1
st
Cross
Zone Device / 2
nd
Cross Zone
Device / Count Zone Device /
Single Release Device
Walktest
Y
Enabled / Disabled
Y
0.1% - 0.99645% ft. (slider)
States
State Assignments
Fire 2 / Fire 1 / Action 2 / Action 1
/ Alert
Y
Disabled
/ Alarm / PreAlarm 2 /
PreAlarm 1 / Supervisory /
Process
3
Y
Latching /
Non-Latching
4
Alarm Verification Timers
Fire 2 / Fire 1 / Action 2 / Action 1
/ Alert
Y
No Timer
/ Timer 1 / Timer 2 /
Timer 3
5
Verification Timer Values
Timer 1 / Timer 2 / Timer 3
Y
0
– 255 (seconds)
Acclimate
Acclimate Y
Enabled /
Disabled
Acclimate High Range
Y
Range 1-H
(0.00046%ft – 0.04980%ft)
Range 2-M
(0.05%ft – 0.09982%ft)
Range 3-M
(0.1%ft – 0.99645%ft)
Range 4-L
(1%ft – 3.98818%ft)
6
Notes:
1.
Cheetah Xi can have up to four (4) addressable loops.
2.
Can be assigned to 4 discrete zones, 2 zone ranges or 1 range and 2 discrete zones.
3.
Each detection level on the FAAST detector can be mapped to a panel state (user defined).
4.
Each detection level can be configured as a latching or non-latching event.
Must be latching if configured for alarm.
5.
Each detection level can be configured to initiate one of three Alarm Verification timers.
6.
Allows you to set the high sensitivity level for the selected acclimate range.
Summary of Contents for 10-068