3.4
Description of parameters
PARA-
Description
Adjustment Range
Lt settings
METER
SP
Setpoint of control
LLit...HLit
P (%)
Manual mode (%)
0...100%
ASP1
Alarm setpoint
If ALm1 = 0, 1, 4 or 5 :
alarm setpoint value
LLit...HLit
200°C
If ALm1 = 2, 3, 6, 7, 8, 9, 10 or
11 : bandwidth
If ALm1 = 12 or 13 : timer
0...3600 minutes
rr
Ramp rate for the process value
If 0
≤
in
≤
9 : 0...200 °C/min.
If in = 10 : 0...3600 unit/min.
0°C/minute
oFSt
Offset value for manual reset
0...100% (« ti » =0)
20.0%
SHiF
Offset shift for process value
-111°...111°C
0°C
Pb
Proportional band
0...200°C
10°C
0% (ON-OFF mode)
ti
Integral time
0...3600 s
120 s
td
Derivative time
0...1000 s
30 s
LoCL
Local mode
0 : no control parameters can be changed
1 : control parameters can be changed
1
SEL
Parameters selection
0 : none
0
(allows selection of additional
1 : ASP1
parameters to be accessible
2 : rr
at Level 0 security, i.e. without
3 : oFSt
having to press key for 6 s).
4 : ASP1, rr
5 : ASP1, oFSt
6 : rr, oFSt
7 : ASP1, rr, oFSt
Ct
Proportional cycle time
0...120 s
Relay output : 20 s
Analogue output : 0 s
Pulsed voltage : 1s
In
Input mode selection
0 : thermocouple J
0
1 : thermocouple K
2 : thermocouple T
3 : thermocouple E
4 : thermocouple B
5 : thermocouple R
6 : thermocouple S
7 : thermocouple N
8 : Pt 100
Ω
(DIN 43.760)
9 : Pt 100
Ω
(JIS C1604-1981)
10 : linear voltage -10...60 mV DC
ALm1
Alarm mode selection
0 : process high alarm
Process alarms are at fixed
1 : process low alarm
1
temperature points. Deviation
2 : deviation high alarm
alarms move with the setpoint
3 : deviation low alarm
value.
4 : inhibit process high alarm
5 : inhibit process low alarm
6 : inhibit deviation high alarm
7 : inhibit deviation low alarm
8 : outband alarm
9 : inband alarm
10 : inhibit outband alarm
11 : inhibit inband alarm
12 : alarm relay On as Dwell Time output
13 : alarm relay Off as Dwell time output