40
3.8. CONSTRUCTION SPECIFICATIONS
Coil
Length (mm)
450
800
1200
Clamping diameter (mm)
120
235
360
Shielded lead 4 mm in diameter between the sensor and the electronic unit:
A110: 2 metres long
A130: 3 metres long
Electronic unit:
Overall dimensions: 120 x 58 x 36 mm
A110: Output by a cable 50 cm long and 2 plugs 4 mm in diameter.
A130: Output by a cable 50 cm long and 3 BNC connectors.
Mass of the device:
A110: approximately 360, 450, and 500 g, depending on the size of the sensor.
A130: approximately 1 kg.
Protection index:
IP 54 for the electronic unit and IP 67 for the flexible sensor per IEC 60529.
The flexible coil stands up well to oils and aliphatic hydrocarbons.
3.9. CONFORMITY TO INTERNATIONAL STANDARDS
Electrical safety per IEC 61010‑2‑032 for type B sensors.
Single-phase electronic unit
and connecting cable to the
measuring instrument
Three-phase electronic unit
and connecting cable to the
measuring instrument
Sensor
and connecting cable to the
electronic unit
Double insulation
Double insulation
Double insulation
Measurement category: IV
Measurement category: III
Measurement category: IV
Rated voltage: 600V
(1)
Rated voltage: 600 V
Rated voltage: 1000 V
(1): or 1000 V in category III.
The 250 V mains adapter (option).
3.10. ELECTROMAGNETIC COMPATIBILITY (CEM)
Emissions and immunity in an industrial environment per IEC 61326‑1.