Trifecta 2K
18
F
USES
The control box has three fuse-holder terminal blocks, which are black and have a lift open
door. The power to the system should be turned off when checking or replacing fuses. To
replace or check a fuse, lift the door open and slide the fuse out of the holder. Slide the new
fuse in place and snap the door back into place. T
ABLE
9 lists the specifications of the fuses in
use, with F
IGURE
6 illustrating the location of the fuses.
R
ESISTOR
E
LEMENTS
The control circuit utilizes precision resistor elements to convert the transmitters’ 4-20mA
current signal to a voltage for the controller to read. The resistors are 500 Ohms and have very
tight tolerances. If a resistor does not measure 500 Ohms within 0.5 Ohms, a new resistor
should be installed. T
ABLE
10 lists the resistor information:
T
ABLE
9 - Fuses
Fuse Type
Size
Capacity
Chart, Inc. Part Number
AGC-10
¼” x 1” (0.7 x 2.54 cm)
10 Amperes
AAA0205
AGC-5
¼” x 1” (0.7 x 2.54 cm
5 Amperes
AAA0204
114 114 114 114 114 114 114 114 114 114 114 114
SH SH SH SH SH SH SH SH SH SH SH SH
114 114 114 114 114 114 114 114 114 114 114 114
201 113 202 113 203 113 204 113 205 113 206 113
SH SH SH SH SH SH SH SH SH SH SH SH
309 310
XI
N
N
N
N
N GND
CR302
CR304
CR306
CR308
CR310
CR312
CR314
CR316
FU104
FU112
FU120
103
104
105
106
108
109
110
111
102
102
102
102
107
107
107
107
201 113 202 113 203 113 204 113 205 113 206 113
113
113
113
113
113
113
113
113
301
302
303
304
305
306
307
308
F
IGURE
6 - Fuse Location Diagram
Tank #1 Solenoid Valves (10A)
Tank #2 Solenoid Valves (10A)
Enclosure Heater (5A)
Fuse Holders (3)
Resistance Value
Tolerance
Chart, Inc. Part Number
500 Ohm
0.1%
10965691
T
ABLE
10 - Resistor Elements