background image

stabilizer should be fitted.

It is important that there is sufficient
draw in the chimney and that the
chimney does not suffer from
down-draught. When the chimney is
warm the draw should be not less
than 2.5mm (0.10 inches) water
gauge. If in doubt about the chimney
seek expert advice.

HEARTH AND FIRE

SURROUND

The stove must stand on a fireproof
hearth and must be situated at least
300mm (12 inches) from any
combustible material. There must be
a gap behind the stove of at least
25mm to allow air to enter the
airwash inlets. The positioning of the
stove and the size of the hearth are
governed by building regulations for
Class 1 appliances. These building
regulations state that the hearth must
extend in front of the stove by at least
300mm (12 inches) and to the sides
of the stove by at least 150mm (6
inches). If in doubt as to the
positioning of the stove expert advice
should be sought either from the
supplier or the local building
inspector.

The fireplace must allow good
circulation of air around the
appliance to ensure that maximum
heat is transferred to the room and
also to prevent the fireplace from
overheating. A gap of 150mm (6
inches) each side and 300mm (12
inches) above the appliance should
give sufficient air circulation. If a
wooden mantelpiece or beam is used
in the fireplace it should be a
minimum of 460mm (18 inches), and
preferably 600mm (24 inches) from
the appliance. In some situations it
may be necessary to shield the beam
or mantelpiece to protect it.

HEALTH AND SAFETY

PRECAUTIONS

Please take care when installing the
stove that the requirements of the
Health and Safety at Work Act 1974
are met.

Some types of fire cement are caustic
and should not be allowed to come
into contact with the skin. In case of
contact wash with plenty of water.

If there is a possibility of disturbing
any asbestos in the course of
installation then please use
appropriate protective equipment.

There must not be an extractor fan
fitted in the same room as the stove
as this can cause the appliance to
emit fumes into the room.

There must be an adequate air supply
into the room in which the appliance
is installed totalling at least 100
square cm. (16 square inches) to
provide combustion air. This is
particularly necessary if the room is
double glazed.

In addition to these instructions the
requirements of BS.8303 and
BS.6461 Pt 1&2; 1984 must be
fulfilled. Local Authority Bylaws and
Building Regulations regarding the
installation of Solid Fuel burning
appliances, flues and chimneys must
also be observed.

PERFORMANCE

The output of the Country 6 is 6.0
kW (20,500 Btu/h). The optional
add-in boiler has an output of 2.9 kW
(10,000 Btu/h), if the boiler is fitted
then the heat output to the room will
be reduced by this amount.

These outputs are based on a 2 hourly
re-fuelling cycle burning seasoned
hardwood logs, or a 4 hourly

re-fuelling cycle burning smokeless
fuel.

CHIMNEY

In order for the appliance to perform
satisfactorily the chimney height
must not be less than 4 metres
measured vertically from the outlet of
the stove to the top of the chimney.
The internal dimensions of the
chimney should preferably be 175
mm (7 inches) or 200mm (8 inches)
either square or round and MUST
NOT BE LESS THAN 150 mm (6
INCHES).

If an existing chimney is to be used it
must be swept and checked, it must
be in good condition, free from
cracks and blockages, and should not
have an excessive cross sectional
area. If you find that the chimney is
in poor condition then expert advice
should be sought regarding the
necessity of having the chimney
lined. If it is found necessary to line
the chimney then a lining suitable for
Solid Fuel must be used.

If there is no existing chimney then a
prefabricated block chimney or a twin
walled insulated stainless steel flue to
BS.4543 can be used either internally
or externally. These chimneys must
be fitted in accordance with the
manufacturers instructions and
Building Regulations.

Anki pumice liners or chimney
blocks will give a highly insulated
chimney which will work well with
all fuels. For details ring (01983)
527997.

Single wall flue pipe is suitable for
connecting the stove to the chimney
but is not suitable for using for the
complete chimney.

If it is found that there is excessive
draw in the chimney then a draught

CHARNWOOD COUNTRY 6

INSTALLATION INSTRUCTIONS

Page 6

Country 6  11/00

Summary of Contents for COUNTRY 6 FT

Page 1: ...Operating and Installation Instructions CHARNWOOD COUNTRY 6 FT ...

Page 2: ...may find it helpful to try several fuels to find the most suitable If you are unable to obtain the fuel you want ask your supplier or an approved fuel distributor to suggest an alternative Only smokeless fuels may be burnt in smoke control areas PETROLEUM COKE IS NOT SUITABLE FOR USE ON THIS APPLIANCE ITS USE WILL INVALIDATE THE GUARANTEE DOOR OPERATION Using the tool turn the right hand door knob...

Page 3: ...ay Never allow the ash to accumulate in the ashpan so that it comes in contact with the underside of the grate as this will seriously damage the grate Care should be taken to ensure that ash is cool before emptying it into plastic liners or bins After emptying the ashpan poke the fire with a poker to clear the firebed of ash To make ash removal easier when burning coal or smokeless fuel there is a...

Page 4: ...s removed from all horizontal surfaces after sweeping In situations where it is not possible to sweep through the appliance the installer will have provided alternative means such as a soot door After sweeping the chimney the appliance flue outlet and the flue pipe connecting the stove to the chimney must be cleaned with a flue brush After clearing any soot from within the stove replace the throat...

Page 5: ...ry seek professional advice The most common cause of fume emission is flueway or chimney blockage For your own safety these must be kept clean Fire blazing out of control Check that a The doors are tightly closed b The airslides are turned down to the minimum setting c The airwash control is closed d A suitable fuel is being used e Door seals and airwash slide are intact Chimney Fires If the chimn...

Page 6: ...supply into the room in which the appliance is installed totalling at least 100 square cm 16 square inches to provide combustion air This is particularly necessary if the room is double glazed In addition to these instructions the requirements of BS 8303 and BS 6461 Pt 1 2 1984 must be fulfilled Local Authority Bylaws and Building Regulations regarding the installation of Solid Fuel burning applia...

Page 7: ...ut the knock outs for the boiler tappings in the back of the firebox Fit one back nut on the flow tapping to come flush with the back face of the boiler and fit the boiler into the appliance Place the fibre washers over the tappings on the outside of the appliance and fit the two remaining backnuts ensuring that the boiler is held tightly against the rear inside face of the appliance and that the ...

Page 8: ... swept The optional vertical rear flue connector does allow the chimney to be swept through the stove except when a boiler is fitted Soot doors may either be in the actual brickwork of the chimney or in the register plate Various positions of soot doors are shown in Figs 4 to 7 PRE LIGHTING CHECK If the optional boiler is fitted then the throat plate is not required If the optional boiler is not f...

Reviews: