background image

should be used. In order to prevent the
build up of scale and corrosion a
suitable inhibitor should be used. The
system must be correctly vented as
shown in Figs. 5 and 6. The height
differential between the header tank
and the appliance must not exceed
15.2 metres (50 feet).

If all four boiler tappings are used
then, if possible, diagonal pairs should
be connected for domestic hot water
and central heating. Where a common
return is used an injector tee must be
incorporated into the system as shown
in Fig. 7. This will ensure that a good
domestic hot water supply is
maintained when the central heating
pump is operating.

The system must incorporate a gravity
circuit which will normally heat the
domestic hot water and an unvalved
radiator with an output of at least 1
kW. When the appliance is not
connected to a domestic hot water
system the unvalved radiator(s) on the
gravity circuit must have an output of
at least 1.25 kW. This is to prevent
boiling in case of pump failure. All
pipework in the primary circuit must
be 28 mm diameter and the gravity
flow pipe must rise continuously from
the boiler to the open vent. Two
typical systems are shown in Figures
5. and 6.

If the appliance is used to heat a small
central heating system then the heat
output to the room from the fire will
be reduced. Fig. 4. shows the ratio of
space heating to water heating which
can be expected.

Fitting a radiator in the same room as
the fire is recommended as it will
allow greater flexibility in the way
that the system is operated as well as
ensuring that there is sufficient heat.

Connect the heating system to the
boiler ensuring that the primary flow
pipe rises continuously from the
appliance to the vent. Fill the system
with water and check for leaks.

The circulating pump may be
controlled by means of time switches,
room thermostats or outdoor
thermostats. Radiators may be either
manually or thermostatically
controlled. These controls will all
work in conjunction with the
thermostat on the appliance and the
low limit pipe thermostat.

We recommend fitting a pipe
thermostat onto the gravity return to

SYSTEM CONTROLS

Page 6

Country 14B 09/03

Central Heating Flow

Central Heating Return

Drain Cock at Lowest Point

Drain Cock

Indirect Hot Water Cylinder

Cold Water Tank

Overflow

Feed and Expansion Tank

22mm Open Vents

Gravity Radiator

Circulating Pump

Central Heating Return

Drain Cock at Lowest Point

Drain Cock

Indirect Hot Water Cylinder

Domestic Hot Water Draw Off

Cold Water Tank

Overflow

Overflow

Feed and Expansion Tank

22mm Open Vents

Gravity Radiator

Circulating Pump

Injector Tee

Minimum Return Thermostat

Gravity Return

(28mm Pipe)

Central Heating Return

Common Return to Boiler

Central Heating Flow

Minimum Return
Thermostat

(28mm Pipe)

Overflow

Domestic Hot Water Draw Off

Fig. 7. Injector Tee.

Using 4 Boiler Tappings

Using 3 Tappings

Fig. 5. Typical Central Heating & Hot Water System

Fig. 6. Typical Central Heating & Hot Water System

Summary of Contents for Country 14B

Page 1: ...stallation Instructions C H A R N W O O D B i s h o p s W a y N e w p o r t I s l e o f W i g h t P O 3 0 5 W S U n i t e d K i n g d o m T 4 4 0 1 9 8 3 5 3 7 7 9 9 F 4 4 0 1 9 8 3 5 3 7 7 8 8 c h a r n w o o d a j w e l l s c o u k w w w c h a r n w o o d c o m ...

Page 2: ...At first you may find it helpful to try several fuels to find the most suitable If you are unable to obtain the fuel you want ask your supplier or an approved fuel distributor to suggest an alternative Use the door opening and ashpan tool to open and close the doors Turn the right hand door knob anti clockwise to open and clockwise to close see Fig 1 Your Charnwood stove is fitted with a multifuel...

Page 3: ...p The ashpans should be emptied regularly before it becomes too full Never allow the ash to accumulate in the ashpans so that it comes in contact with the underside of the grate as this will seriously damage the grate bars The ashpans are handled using the tool provided Care should be taken to ensure that ash is cool before emptying it into plastic liners or bins To make ash removal easier there i...

Page 4: ...y the appliance flue outlet and the flue pipe connecting the stove to the chimney must be cleaned with a flue brush After clearing any soot from within the stove replace the throat plate see Fig 3 the front firebars and side fireplates Different types of sweep s brushes are available to suit different flueways For standard brick chimneys a wire centre sweep s brush fitted with a guide wheel is rec...

Page 5: ...ed d the fire is not fitted onto a heating system which is too large Do not light the fire if there is any possibility that any parts of the system may be frozen Check that a the fire is burning properly if not then carry out the checks under Fire Will Not Burn Over Firing Freezing Lack of Heat To Radiators Hot Water b the throat plate is fitted correctly see Fig 3 and that it is not distorted c t...

Page 6: ...himney is in poor condition then expert advice should be sought regarding the necessity of having the chimney lined If it is found necessary to line the chimney then a lining suitable for Solid Fuel must be used If there is no existing chimney then a prefabricated block chimney or a twin walled insulated stainless steel flue to BS 4543 can be used either internally or externally These chimneys mus...

Page 7: ...e expected Fitting a radiator in the same room as the fire is recommended as it will allow greater flexibility in the way that the system is operated as well as ensuring that there is sufficient heat Connect the heating system to the boiler ensuring that the primary flow pipe rises continuously from the appliance to the vent Fill the system with water and check for leaks The circulating pump may b...

Page 8: ...ugh the appliance but in most back outlet installations it will be necessary to have a soot door to enable the chimney to be swept This may either be in the actual brickwork of the CONNECTIONS TO FLUES SOOT DOORS chimney or in the register plate Various types and positions of soot doors are shown in figures 8 to 10 Before lighting the fire check the cold setting distance of the thermostat Remove t...

Page 9: ...of the installation and after allowing a suitable period of time for the fire cement and mortar to dry out the stove should be lit and checked to ensure that smoke and fumes are taken from the appliance up the chimney and emitted safely Also check all joints and seals COMMISSIONING The central heating pump should be adjusted to give the correct water flow against the circuit resistance and the sys...

Page 10: ... 49 010 BW51 Ash Carrier Optional Extra 14 004 FV15 Secondary Air Rod 50 008 TH02 L Low Level Pipe Stat Opt l Extra 15 002 EW15 Side Fire Plate 51 002 DY18 R H Door Knob Spindle 16 002 BV16 Back Fire Plate 52 002 KV14 Door Catch Cam 17 002 CG01 Bottom Grate Bar 18 002 CG01S14 Set of Grate Bars 14 per set 19 004 FV17L Left Hand Ashpan 20 004 FV17R Right Hand Ashpan 21 004 BV19 Ash Shedding Plate 22...

Page 11: ... a y N e w p o r t I s l e o f W i g h t P O 3 0 5 W S U n i t e d K i n g d o m T 4 4 0 1 9 8 3 5 3 7 7 9 9 F 4 4 0 1 9 8 3 5 3 7 7 8 8 c h a r n w o o d a j w e l l s c o u k w w w c h a r n w o o d c o m Your Local Charnwood Dealer ...

Reviews: