background image

HEALTH AND SAFETY

PRECAUTIONS

PERFORMANCE

Please take care when installing the
stove that the requirements of the
Health and Safety at Work Act 1974
are met.

Some types of fire cement are caustic
and should not be allowed to come
into contact with the skin. In case of
contact wash with plenty of water.

If there is a possibility of disturbing
any asbestos in the course of
installation then please use appropriate
protective equipment.

There must not be an extractor fan
fitted in the same room as the stove as
this can cause the appliance to emit
fumes into the room.

There must be an adequate air supply
into the room in which the appliance is
installed totalling at least 100 square
cm. (16 square inches) to provide
combustion air. This is particularly
necessary if the room is double glazed.

Do not light the fire before the boiler
has been connected to the system and
filled with water, as this can cause
serious damage to the boiler.

In addition to these instructions the
requirements of BS.8303 and BS.6461
Pt 1&2; 1984 must be fulfilled. Local
Authority Bylaws and Building
Regulations regarding the installation
of Solid Fuel burning appliances, flues
and chimneys must also be observed.

The output of the Country 14B is 10.5
kW (35,800 Btu/h) to water and 3.7
kW (12,600 Btu/h) to the room. The
outputs were obtained burning
smokeless fuel over a four hourly re-
fuelling cycle with the doors closed.

The heat output to the room is directly
proportional to the heat output to
water as shown in Fig. 4. This means
that if the water heating load is less
than the rated output then the room
heating will be reduced by the same
proportion. This must be borne in
mind when calculating the heating
requirements.

CHIMNEY

In order for the appliance to perform
satisfactorily the chimney height must
not be less than 4 metres measured
vertically from the outlet of the stove
to the top of the chimney. The internal
dimensions of the chimney should
preferably be 175 mm (7 inches) or
200mm (8 inches) either square or
round and MUST NOT BE LESS
THAN 150 mm (6 INCHES).

If an existing chimney is to be used it
must be swept and checked, it must be
in good condition, free from cracks
and blockages, and should not have an
excessive cross sectional area (e.g.
greater than 250mm x 250mm). If you
find that the chimney is in poor
condition then expert advice should be
sought regarding the necessity of
having the chimney lined. If it is
found necessary to line the chimney

then a lining suitable for Solid Fuel
must be used.

If there is no existing chimney then a
prefabricated block chimney or a twin
walled insulated stainless steel flue to
BS.4543 can be used either internally
or externally. These chimneys must be
fitted in accordance with the
manufacturers instructions and
Building Regulations.

Single wall flue pipe is suitable for
connecting the stove to the chimney
but is not suitable for using for the

complete chimney.

If it is found that there is excessive
draw in the chimney then a draught
stabilizer should be fitted.

It is important that there is sufficient
draw in the chimney and that the
chimney does not suffer from down-
draught. When the chimney is warm
the draw should be not less than 2.54
mm (0.10 inches) water gauge. If in
doubt about the chimney seek expert
advice.

The stove must stand on a fireproof
hearth and must be situated at least
300mm (12 inches) from any
combustible material. The positioning
of the stove and the size of the hearth
are governed by building regulations
for Class 1 appliances. These building
regulations state that the hearth must
extend in front of the stove by at least
300mm (12 inches) and to the sides of
the stove by at least 150mm (6
inches). If in doubt as to the
positioning of the stove expert advice
should be sought either from the
supplier or the local building
inspector.

The fireplace must allow good
circulation of air around the appliance
to ensure that maximum heat is
transferred to the room and also to
prevent the fireplace from
overheating. A gap of 150mm (6
inches) each side and 300mm (12
inches) above the appliance should
give sufficient air circulation. If a
wooden mantelpiece or beam is used
in the fireplace it should be a
minimum of 460mm (18 inches), and
preferably 600mm (24 inches) from
the appliance. In some situations it
may be necessary to shield the beam
or mantelpiece to protect it.

The central heating system must
comply with BS:5449 part 1.

If the system is to be a combined
heating and domestic hot water system
then a double feed indirect hot water
storage cylinder to BS:1556 part 1

HEARTH AND FIRE

SURROUND

CENTRAL HEATING

SYSTEM

INSTALLATION INSTRUCTIONS FOR THE

CHARNWOOD COUNTRY 14B

Page 5

Country 14B 09/03

Boiler

Output

Space Output

(kW)

(kW)

Fig. 4. Performance Chart

2.0

4.0

6.0

8.0

10.0

12.0

0

1.0

2.0

3.0 4.0

0

Summary of Contents for Country 14B

Page 1: ...stallation Instructions C H A R N W O O D B i s h o p s W a y N e w p o r t I s l e o f W i g h t P O 3 0 5 W S U n i t e d K i n g d o m T 4 4 0 1 9 8 3 5 3 7 7 9 9 F 4 4 0 1 9 8 3 5 3 7 7 8 8 c h a r n w o o d a j w e l l s c o u k w w w c h a r n w o o d c o m ...

Page 2: ...At first you may find it helpful to try several fuels to find the most suitable If you are unable to obtain the fuel you want ask your supplier or an approved fuel distributor to suggest an alternative Use the door opening and ashpan tool to open and close the doors Turn the right hand door knob anti clockwise to open and clockwise to close see Fig 1 Your Charnwood stove is fitted with a multifuel...

Page 3: ...p The ashpans should be emptied regularly before it becomes too full Never allow the ash to accumulate in the ashpans so that it comes in contact with the underside of the grate as this will seriously damage the grate bars The ashpans are handled using the tool provided Care should be taken to ensure that ash is cool before emptying it into plastic liners or bins To make ash removal easier there i...

Page 4: ...y the appliance flue outlet and the flue pipe connecting the stove to the chimney must be cleaned with a flue brush After clearing any soot from within the stove replace the throat plate see Fig 3 the front firebars and side fireplates Different types of sweep s brushes are available to suit different flueways For standard brick chimneys a wire centre sweep s brush fitted with a guide wheel is rec...

Page 5: ...ed d the fire is not fitted onto a heating system which is too large Do not light the fire if there is any possibility that any parts of the system may be frozen Check that a the fire is burning properly if not then carry out the checks under Fire Will Not Burn Over Firing Freezing Lack of Heat To Radiators Hot Water b the throat plate is fitted correctly see Fig 3 and that it is not distorted c t...

Page 6: ...himney is in poor condition then expert advice should be sought regarding the necessity of having the chimney lined If it is found necessary to line the chimney then a lining suitable for Solid Fuel must be used If there is no existing chimney then a prefabricated block chimney or a twin walled insulated stainless steel flue to BS 4543 can be used either internally or externally These chimneys mus...

Page 7: ...e expected Fitting a radiator in the same room as the fire is recommended as it will allow greater flexibility in the way that the system is operated as well as ensuring that there is sufficient heat Connect the heating system to the boiler ensuring that the primary flow pipe rises continuously from the appliance to the vent Fill the system with water and check for leaks The circulating pump may b...

Page 8: ...ugh the appliance but in most back outlet installations it will be necessary to have a soot door to enable the chimney to be swept This may either be in the actual brickwork of the CONNECTIONS TO FLUES SOOT DOORS chimney or in the register plate Various types and positions of soot doors are shown in figures 8 to 10 Before lighting the fire check the cold setting distance of the thermostat Remove t...

Page 9: ...of the installation and after allowing a suitable period of time for the fire cement and mortar to dry out the stove should be lit and checked to ensure that smoke and fumes are taken from the appliance up the chimney and emitted safely Also check all joints and seals COMMISSIONING The central heating pump should be adjusted to give the correct water flow against the circuit resistance and the sys...

Page 10: ... 49 010 BW51 Ash Carrier Optional Extra 14 004 FV15 Secondary Air Rod 50 008 TH02 L Low Level Pipe Stat Opt l Extra 15 002 EW15 Side Fire Plate 51 002 DY18 R H Door Knob Spindle 16 002 BV16 Back Fire Plate 52 002 KV14 Door Catch Cam 17 002 CG01 Bottom Grate Bar 18 002 CG01S14 Set of Grate Bars 14 per set 19 004 FV17L Left Hand Ashpan 20 004 FV17R Right Hand Ashpan 21 004 BV19 Ash Shedding Plate 22...

Page 11: ... a y N e w p o r t I s l e o f W i g h t P O 3 0 5 W S U n i t e d K i n g d o m T 4 4 0 1 9 8 3 5 3 7 7 9 9 F 4 4 0 1 9 8 3 5 3 7 7 8 8 c h a r n w o o d a j w e l l s c o u k w w w c h a r n w o o d c o m Your Local Charnwood Dealer ...

Reviews: