LT93–PS1230–1
5
Charles Industries, Ltd. All rights reserved. Printed in the United States of America.
To AC
ground bus
(green)
WHT BLK GRN
TB1
TB2
40A/32V F
A
S
T
ACTING
SLO–BLO
F2
Note 1
To AC hot (black)
To AC neutral bus (white)
Notes
1. AC stranded wire.
2. DC stranded wire.
3. Optional Splash Guard, part # 21-104589.
4. Internal fuse size is for 30-amp model. See Table 4 for 15- and 30-amp model fuse size.
PCB
DC
Fuse
(see Table
4 & Note 4)
AC
Fuse
(see Table
4 & Note 4)
AC power source
circuit breaker
(min. size15 amps)
F1
(PS2430 shown)
15A/250V
Access to PCB:
and
TB1 & TB2
F1, F2 & F3 Fuses
+DC
–DC
LOAD
+
–
Note 2
Note 3
F3
Figure 1. C-Power 15- & 30-Amp Block Diagram
Choosing Wire Gauge
Use Table 2 and Table 3 to determine the appropriate wire gauges. Avoid unnecessarily long runs of either AC or
DC power lines.
Before working on electrical equipment, first determine there is no live power! Double check power
connections.
DANGER
Table 2.
Minimum Wire Size to Input of CPower
120 VAC SHORE POWER INPUT TO C-POWER
Model Number
AC Amp Max
25’ Length
50’ Length
100’ Length
PS2415
10
16 AWG
14 AWG
10 AWG
PS2430
12
14 AWG
12 AWG
10 AWG
PS1230
10
16 AWG
14 AWG
10 AWG
220 VAC SHORE POWER INPUT TO C-POWER
PS2415
5
18 AWG
16 AWG
14 AWG
PS2430
6
16 AWG
14 AWG
12 AWG
PS1230
5
18 AWG
16 AWG
14 AWG