FACTORY DEFAULT SETTINGS
Table 7 shows the factory default settings using a 12V battery. Table 8 shows the factory default settings using a
24V battery.
Table 7. Factory Default Settings with a 12V Battery
Variable Settings
Default
Units
Gel (Bulk Mode)
14.2
Volts
Gel (Float Mode)
13.6
Volts
NiCAD (Equalize Mode)
14.5
Volts
NiCAD (Float Mode)
14.0
Volts
AGM (Bulk Mode)
14.2
Volts
AGM (Float Mode)
13.4
Volts
Lead Acid (Bulk Mode)
14.5
Volts
Lead Acid (Float Mode)
13.1
Volts
Bulk/Equalize Duration
0.2
Days
Equalize Cycle
30.0
Days
Equalize Voltage *
(Lead Acid)
15.5
Volts
Equalize Time *
1.0
Hours
Temperature
Fahrenheit
Degrees
Audio Alarm
On
Password
Disabled
*
Not a changeable parameter
Lead Acid and NiCAD batteries only
Table 8. Factory Default Settings with a 24V Battery
Variable Settings
Default
Units
Gel (Bulk Mode)
28.4
Volts
Gel (Float Mode)
27.2
Volts
NiCAD (Equalize Mode)
29.0
Volts
NiCAD (Float Mode)
28.0
Volts
AGM (Bulk Mode)
28.4
Volts
AGM (Float Mode)
26.8
Volts
Lead Acid (Bulk Mode)
29.0
Volts
Lead Acid (Float Mode)
26.2
Volts
Bulk/Equalize Duration
0.2
Days
Equalize Cycle
30.0
Days
Equalize Voltage *
(Lead Acid)
31.0
Volts
Equalize Time *
1.0
Hours
Temperature
Fahrenheit
Degrees
Audio Alarm
On