LT‐IMCHRGR120‐1
Issue 1 Print 2
17
Copyright 2013 Charles Industries, Ltd. All rights reserved. Printed in the United States of America.
Bank Voltage Summary
Each bank’s nominal output voltage (12VDC, 24VDC, or Off)
is shown. This display alternates with Bank Battery Type
Summary. Select EDIT to modify a bank.
Select NEXT to move on to general charger option setup.
Bank Battery Type Summary
Each bank’s battery type is shown. The bank types are as
follows: FBO=Fixed Bank Output, GEL=Gel Cell, LA=Flooded
Lead Acid, AGM=Absorbed Glass Mat, NCD=NiCad, “−”=
Bank not used. This display alternates with Bank Battery Type
Summary. Select EDIT to modify a bank.
Select NEXT to move on to general charger option setup.
Individual Bank Summary
A bank’s detail settings are displayed here. This includes the
bank type, the nominal bank voltage, and the maximum amps.
Select EDIT to modify this bank’s characteristics.
Select NEXT to move to the next bank.
Bank Enable
Turns on/off a bank. Turn off banks that are not used to pre-
vent alarms and aid in charging.
Turn on banks that are connected to batteries.
Bank Voltage Select
Select the nominal output voltage of the battery bank.
Warning:
Battery Voltage must be set properly. Failure to set the
charger to the proper battery voltage range will perma-
nently damage the charger and the batteries and may
cause a risk of fire.
Avertissement:
Tension de pile doit être réglée convenablement. L’échec
pour régler le chargeur à la gamme de tension de pile
correcte endommagera d’une façon permanente le char-
geur et les piles et peut causer un risque de feu.