LT‐IMCHRGR120‐1
Issue 1 Print 2
13
Copyright 2013 Charles Industries, Ltd. All rights reserved. Printed in the United States of America.
Step
Action
Result
1.
At the end of setup, there is an option
to Save or Cancel the changes just
made. Cancel returns to the previous-
ly unchanged values. Save stores the
values in the memory button.
Important Notes
The Charger output is turned off during Setup and will automatically restart after Setup mode is
completed.
Keypad Timeout: If no keys are pressed for approximately 5 minutes, the system will return to
normal operation, which is equivalent to pressing the Cancel key.
The system must be Setup before the 1
st
operation. Cancel is replaced with Restart. Keypad
Timeout is disabled.
The Smart Memory Button must be in−place for Setup to operate properly.
Switching battery types will restore all battery related setting on that bank to factory defaults.
Configuration Storage
All the configuration and settings are stored in the Smart Memory Button. This non−volatile memory can be
moved from charger to charger if necessary.
During system startup and operation, the Smart Memory Button is referenced for setting and configuration neces-
sary to operation the charger. For this reason, the Smart Memory Button must be present at all times during
charger operation.
Table 4. Setup Menu Options
Menu Option
Type
Description
Battery Voltage
Selectable
Set to the nominal voltage of the battery connected.
Warning:
Battery Voltage must be set properly. Failure to set the charger to the
proper battery voltage range will permanently damage the charger and
the batteries and may cause a risk of fire.
Avertissement:
Tension de pile doit être réglée convenablement. L’échec pour régler le
chargeur à la gamme de tension de pile correcte endommagera d’une
façon permanente le chargeur et les piles et peut causer un risque de
feu.
Battery Type
Selectable
Set to the type of battery connected.
Note:
A small arrow in the lower corner of the display screen indicates that
additional battery selections are available. FBO (Fixed Bank Output),
LA (Lead Acid), NCD (NiCad), AGM, GEL.
Note:
FBO (Fixed Bank Output) is only available on bank 1.
The following selections are available from the Custom Settings Menu.