— 2 —

Basic Function and Design

The CHANCE® Auto-Ranging Voltage Indicator (“ARVI”) is a portable tool to
confirm that a high-voltage line is de-energized prior to performing mainte-
nance. It presents field practicality over a voltmeter and obvious advantages
over traditional methods without a meter. Readings from the ARVI represent the
class of voltage that is present on the line.

The C403-3374 is designed to determine phase-to-phase voltage classes up to
69kV. The C403-3375 is designed to determine phase-to-phase voltage classes up
to 500kV. Both units consist of one section of Epoxiglas

®

 pole with high internal

impedance that is encapsulated to prevent moisture penetration and mechanical
damage.

The ARVI is actually an electric field intensity meter, which is calibrated to
illuminate an LED (light-emitting diode) representing the class of voltage that
is present on the conductor. It responds to the magnitude of the field gradient
between its end probe and a floating electrode. The device indicates the combined
field intensity from all other conductors, including ground wires and grounded
equipment. If the universal fitting is close to a ground, another phase, or another
voltage source the voltage indication will tend to be high. If the universal fitting
is close to a jumper or equipment of the same phase, the indication will tend to
be low. The tool must be used with a universal pole to maintain its calibration.

The ARVI can be used as a secondary means to confirm the condition of a circuit
after principal work procedures such as visible open gaps, dispatcher hold
orders, and apparatus tag-outs have rendered the circuit de-energized.

Operation — General

To turn the unit on press and release the “Power” push button.  Upon power-up
each LED will illuminate individually from the lowest voltage to the highest
followed by the audible alarm. These tests verify the function of the LED’s,
alarm, batteries, and internal circuitry. Full unit function can only be verified
using a known energized high voltage source or with the appropriate Voltage
Indicator Tester (C403-3409 for C403-3374 ARVI and C403-3431 Voltage Indi-
cator Tester for C403-3375 ARVI). Following the audible alarm the “Power / Low-
Battery” LED will flash indicating that the unit is ready for use. After use turn
the unit off by holding the power switch until the power LED turns off, or the unit
will power itself down after approximately 15 minutes of inactivity.

The unit will begin to make an audible beep and an LED will blink when the unit
senses an electric field, even when not making contact with an energized
conductor. The higher the voltage, the faster the beeping occurs. If the unit
senses constant voltage for approximately 15 seconds, it automatically goes into
its hold-mode. At that point the LED representing the voltage class being
indicated will light continuously and the beeping will become continuous for 1 to
2 seconds followed by 5 to 6 very rapid beeps and a brief period of silence. The unit
then will return to the normal audible mode, but one LED will remain solid until
reset. Remove the unit from the line and press and release the power switch to
reset the unit.

Once in the Auto-Hold mode, the ARVI must be reset for the LED's to indicate higher
or lower voltages.

!

CAUTION

Summary of Contents for C403-3374

Page 1: ...to installation operation or maintenance Should additional information and details be desiredorifsituationsarisewhicharenotcoveredadequatelyfortheuser spurpose the specifics should be referred to Hubbell Power Systems Chance Before operating a CHANCE Auto Ranging Voltage Indicator thoroughly read understand and follow these instructions Keep these instructions in the device case for future referen...

Page 2: ...ible open gaps dispatcher hold orders and apparatus tag outs have rendered the circuit de energized Operation General To turn the unit on press and release the Power push button Upon power up each LED will illuminate individually from the lowest voltage to the highest followed by the audible alarm These tests verify the function of the LED s alarm batteries and internal circuitry Full unit functio...

Page 3: ... from all system components other than the specific conductor being tested Auto Hold The ARVI has a hold feature built into the circuitry which automatically holds a reading when the unit is left on an energized conductor or senses constant voltage for a period of approximately 15 seconds In the hold mode the LED representing the voltage range being indicated will become solid The audible beeping ...

Page 4: ...her part even with rubber gloves will cause erroneous voltage indication Always use with a universal pole to maintain its calibration Test phase Electromagnetic action of current Both can induce a high static condition on the de energized circuit Activity shown between only two conductors for clarity here Similar effects exist between all conduc tor pairs ARVI indicates the combined field intensit...

Page 5: ...per length to maintain its calibration When using the ARVI on underground systems the same basic rules and procedures apply as with overhead for example maintaining proper working clearances to all parts of the tool keeping tool clean and dry However the following are two additional instructions when using the tool on underground equipment The readings taken in URD cabinets will typically be highe...

Page 6: ...ull elbow with elbow pullertool thenorientelbowsoitisaccessiblewithARVI Operator 2 install elbow adapter on ARVI then insert elbow adapter into elbow to check elbow cable for voltage 1 Due to the close proximity of energized parts and grounded surfaces probes must not be used when using the ARVI on live front URD equipment because probes could either bridge from phase to phase or phase to ground o...

Page 7: ...k of the panel noting proper polarity CAUTION Ensure that the wires connected to the orange connector in the panel assembly remains connected and arenotdamagedandthebatterystrapissecure Afterthepanelandscrews are replaced in the housing test the function of the unit on a known energized voltage source or with the Voltage Indicator Tester After replacing batteries ensure that the wires connected to...

Page 8: ...le Bag for two 8 universal poles Auto Ranging Voltage Indicator 600V 69kv C403 3409 T403 0857 T403 0856 Repair If repair calibration or parts are required please contact M W Bevins Co 9903 E 54th St Tulsa OK 74146 918 627 1273 918 627 1294 FAX www mwbevinsco com Specifications Operating temp 20 to 80 C Unit power Four 4 AAA batteries C403 3409 Voltage Indicator Tester Care The ARVI is an electroni...

Reviews: