This tool is not intended for continuous contact applications. Contact with
energized conductor should be limited to the amount of time required to note
indication.

To determine the approximate phase-to-phase voltage:

1.  Check battery and circuitry for proper operation by pressing and releasing the

power switch. Verify full unit function by contacting with a known energized
high voltage source or with the appropriate Voltage Indicator Tester (C403-
3409 for C403-3374 ARVI and C403-3431 Voltage Indicator Tester for C403-
3375 ARVI).

2.  Thread the hook probe into the end fitting of the ARVI and attach universal

fitting to an insulated hot stick of proper length for system voltage involved.

Always use appropriate length stick even if wearing rubber gloves.

Contact with universal ferrule or other part even with rubber gloves will cause
erroneous voltage indication.

Always use with a universal pole to maintain its calibration.

Test
phase

*Electromagnetic
action of
current

* Both can induce a

high static condition
on the de-energized
circuit.  (Activity
shown between only
two conductors for
clarity here.  Similar
effects exist
between all conduc-
tor pairs.)

ARVI indicates the combined field
intensity from all other conductors,
including ground wires.

De-energized
circuit

Energized
circuit

*Electrostatic
action of
voltage

Keep instrument clean and dry.
Do not allow universal fitting to become grounded or contact another phase as this
will cause erroneous voltage indication and could cause severe personal injury or
damage to equipment.

Always maintain proper working clearance between operator and all energized parts
of the ARVI by using proper length universal pole.  Failure to follow these warnings
could result in personal injury or damage to equipment.

Operation — Overhead

!

CAUTION

!

WARNING

Summary of Contents for C403-3374

Page 1: ...to installation operation or maintenance Should additional information and details be desiredorifsituationsarisewhicharenotcoveredadequatelyfortheuser spurpose the specifics should be referred to Hubbell Power Systems Chance Before operating a CHANCE Auto Ranging Voltage Indicator thoroughly read understand and follow these instructions Keep these instructions in the device case for future referen...

Page 2: ...ible open gaps dispatcher hold orders and apparatus tag outs have rendered the circuit de energized Operation General To turn the unit on press and release the Power push button Upon power up each LED will illuminate individually from the lowest voltage to the highest followed by the audible alarm These tests verify the function of the LED s alarm batteries and internal circuitry Full unit functio...

Page 3: ... from all system components other than the specific conductor being tested Auto Hold The ARVI has a hold feature built into the circuitry which automatically holds a reading when the unit is left on an energized conductor or senses constant voltage for a period of approximately 15 seconds In the hold mode the LED representing the voltage range being indicated will become solid The audible beeping ...

Page 4: ...her part even with rubber gloves will cause erroneous voltage indication Always use with a universal pole to maintain its calibration Test phase Electromagnetic action of current Both can induce a high static condition on the de energized circuit Activity shown between only two conductors for clarity here Similar effects exist between all conduc tor pairs ARVI indicates the combined field intensit...

Page 5: ...per length to maintain its calibration When using the ARVI on underground systems the same basic rules and procedures apply as with overhead for example maintaining proper working clearances to all parts of the tool keeping tool clean and dry However the following are two additional instructions when using the tool on underground equipment The readings taken in URD cabinets will typically be highe...

Page 6: ...ull elbow with elbow pullertool thenorientelbowsoitisaccessiblewithARVI Operator 2 install elbow adapter on ARVI then insert elbow adapter into elbow to check elbow cable for voltage 1 Due to the close proximity of energized parts and grounded surfaces probes must not be used when using the ARVI on live front URD equipment because probes could either bridge from phase to phase or phase to ground o...

Page 7: ...k of the panel noting proper polarity CAUTION Ensure that the wires connected to the orange connector in the panel assembly remains connected and arenotdamagedandthebatterystrapissecure Afterthepanelandscrews are replaced in the housing test the function of the unit on a known energized voltage source or with the Voltage Indicator Tester After replacing batteries ensure that the wires connected to...

Page 8: ...le Bag for two 8 universal poles Auto Ranging Voltage Indicator 600V 69kv C403 3409 T403 0857 T403 0856 Repair If repair calibration or parts are required please contact M W Bevins Co 9903 E 54th St Tulsa OK 74146 918 627 1273 918 627 1294 FAX www mwbevinsco com Specifications Operating temp 20 to 80 C Unit power Four 4 AAA batteries C403 3409 Voltage Indicator Tester Care The ARVI is an electroni...

Reviews: