background image

4

110498-3

Maintenance

WARNING :

  Before doing any maintenance be sure power 

is off.  At the time you remove either inspection panel be sure to 
unplug motor and pumps.  This is for your safety.

Spring Start-Up

• 

Clean pads.

  A clean pad is more absorbent, effi cient and will give 

more cool air.  Annually, or when required, using a garden hose 
with nozzle, back wash to clean out the openings, then clean off 
the inlet face any scale or other obstruction to the passages.  Slight 
scraping may be required to remove hardened scale.

• 

Change pads if necessary. 

 The pads should be replaced after 5 

years or if necessary.  To change pads, remove top access panel, 
remove grill, and disconnect water delivery tube.  Remove water 
distributor holder and lift out media sections.  Replace with the 
same type media.  You can purchase them from your dealer.  

 

IMPORTANT:

  In order to get the best performance from your 

cooling pads, they must be installed properly.  If you have pur-
chased a pad with two equal angles, the following instructions can 
be disregarded.  Pads must always be installed with the steeper 
fl ute angle sloping down 
towards the air entering 
side (Fig. 7).  The reason 
is simple.  The steeper 
angle puts more water on 
the hot, dry, dirty side of 
the pad where it is needed 
most.  It also counteracts 
the tendency of the air to 
push the water toward the 
back of the pad.

 
• 

Check belt tension.

  A 3 lb. force 

should defl ect the belt     3/4 inches 
(see Fig. 8).  Readjust belt if needed.

• 

Oil bearings.

  The blower bearings 

and cooler motor in this unit should be oiled with a few drops of 
non-detergent 20/30 weight oil once each year.  The motor does 
not need oil if it has no oil lines for oiling.  Motors that have no oil 
lines are lifetime oiled at the factory and require no further oiling 
for the life of the unit.

CAUTION:

  Do not over oil. 

 Over oiling can cause motor burn 

out, due to excessive oil getting into motor winding.

• 

Clean water pump and dump pump.

  Cleaning both pumps is 

necessary once a year at start-up.  For your safety, turn unit off 
and unplug motor and pumps.  Remove the pump from the mount 
slot.  Remove the base of the pump as shown in Fig. 9.  Clean the 
pump and turn the impeller to ensure free operation.  Remove the 
pump spout and check for any blockage.  After cleaning, reinstall 
the base onto the pump.  Press 
fi rmly to make sure it is secure.  
Reattach the pump to the mount 
in the cooler using the plastic 
retainer to ensure that the pump 
will not overturn.  Do not forget 
to replace the spout and water 
delivery tube onto the pump 
outlet.

Winter Shut-Down

• 

Drain water. 

 Always drain all of the water out of the cooler and 

water supply line when not in use for prolonged periods, and par-
ticularly at the end of the season.  Keep the water line disconnected 
from both the unit and water supply so that it does not freeze.

• 

Unplug motor and pumps.

  When cooler is not used for extended 

periods unplug the motor and pumps from inside cooler.

• 

Cover unit. 

 To protect the life of the fi nish, a cover for the unit is 

suggested in extended periods of non use.

By following the operating, installation, and maintenance suggestions 
as outlined, you can get many years of efficient and satisfactory service 
from your cooler.  In the event additional information is desired, your 
dealer will be more than glad to assist you in every possible way.

Required Exhaust Openings

An often misunderstood concept of evaporative cooling is the amount 
of air that should be exhausted.  How much should you open your 
windows?  The fact is that most people do not open their windows 
enough.  The following two methods will help you determine the 
amount to open your windows.

First Method

You should allow an opening of at least 2 square feet (288 square 
inches) for each 1000 CFM rating of your unit.  

Example:

  At 3790 

CFM, model AD1C51 (3/4 hp) requires 7.6 square feet (1094 square 
inches) of opening  (3790/1000 * 2 = 7.6).  Multiply the number of 
windows by window width in inches and divide this into the number 
of square inches required for your size unit.  This will give you the 
height to open windows.  In this example, four 36 inch wide windows 
should be opened 7.6 inches each.

Champion Air Balancing Method

1.  Take a piece of tissue paper and cut it lengthwise into 3 equal 

strips.

2.  Turn your cooler on high cool.
3.  Open one window at least six inches wide in each room that you 

want to cool.

4.  Take the piece of tissue paper and put it up against the screen of 

the open window furthest from the cooler discharge opening.  Let 
go of it.  It will do one of three things.

IF

 

It falls down.

THEN

 

CLOSE all of the windows one inch and try step 4 again.

IF

 

It plasters itself to the screen.

THEN

 

OPEN all of the windows one inch and try step 4 again.

IF

 

It stays on the screen lightly.

THEN

 

PERFECT.  You are done.  Enjoy your cooler.

NOTES:

•  When switching to low cool, you must rebalance your home.  Repeat 

step 4.

•  Once you balance your home you can cool some areas more than 

others by opening those windows more and closing the others by 
the same amount.  Repeat step 4 to make sure your home is still air 
balanced.

45°

15°

Entering 

Air

Leaving Air

Fig. 7

Fig. 8

3 Lb.

3/4 Inches

Impeller

Remove

Base

Fig. 9

Summary of Contents for AU2C711

Page 1: ...ol en el interior 110498 3 9 09 www championcooler com Table Of Contents Safety Instructions 1 Installation Instructions 2 3 Electrical Wiring Diagram 3 Operation 3 4 Maintenance Section 4 Troublesho...

Page 2: ...unit by threading the chase nip ple into the switch box Run the three switch leads through the nipple and into the switch box and reinstall the junction box Connect the green ground lead to the ground...

Page 3: ...ol button again deactivates this mode The Set temperature the target temperature for control may be altered by repeatedly pressing or holding the Up and Down buttons The LCD will display Set rather th...

Page 4: ...the spout and water delivery tube onto the pump outlet Winter Shut Down Drain water Always drain all of the water out of the cooler and water supply line when not in use for prolonged periods and par...

Page 5: ...nit control box 5 Incorrect wiring be tween wall thermostat and cooler 6 Poor connection to Fan motor terminals 7 Unit control board or wall thermostat faulty 1 Insufficient air exhaust 2 Belt too loo...

Page 6: ...a El Medio Evaporativo Izquierdo 281043 001 281045 001 281044 001 281046 001 30 Water Distributor Housing Caja Del Distribuidor De Agua 281038 001 281033 001 281038 001 281033 001 31 Water Distributor...

Page 7: ...7 110498 3 Replacement Parts Piezas De Repuesto AD1C51 AD2C51 AD1C5112 AD2C5112 AD1C71 AD2C71 AD1C7112 AD2C7112...

Page 8: ...45 002 281044 002 281046 002 29 Media Shield Left Protector Para El Medio Evaporativo Izquierdo 281043 001 281045 001 281044 001 281046 001 30 Water Distributor Housing Caja Del Distribuidor De Agua 2...

Page 9: ...9 110498 3 Replacement Parts Piezas De Repuesto AS1C51 AS2C51 AS1C5112 AS2C5112 AS1C71 AS2C71 AS1C7112 AS2C7112...

Page 10: ...Del Distribuidor De Agua 3D 23 32 Evaporative Media Medio Evaporativo 310118 002 33 Distributor Filter Pad Filtro Del Distribuidor 110120 34 Water Reservoir Bandeja Acumuladora De Agua 281042 35 Tube...

Page 11: ...11 110498 3 Replacement Parts Piezas De Repuesto AU1C7112 AU2C7112...

Page 12: ...l aire viejo Se reemplaza completamente el aire cada 2 a 4 minutos abriendo las ventanas o las puertas o una combinaci n de ambas El aire es siempre fresco no es viciado cargado de humo y olores como...

Page 13: ...encuentra en el interior del panel central v ase Fig 5 Por dentro de la unidad inserte la niple roscada a trav s del agujero de acceso el ctrico Resbale el anillo de estanquidad sobre la niple roscad...

Page 14: ...est funcionando en el modo Cool o Fan cuando presiona el bot n Timer el periodo de retraso se determina cuando el enfriador apagar Si el enfriador est apagada cuando presiona el bot n Timer el per od...

Page 15: ...pecto a cualquier duda o pregunta Cuanto Debe Abrir Las Ventanas Un concepto a menudo entendido mal de enfriamiento por evaporaci n es la cantidad de aire que debe ser agotada Cu nto debe usted abrir...

Page 16: ...ivo no est mojado Filtros obstruidos Agujeros del tubo obs truidos Bomba no funciona 1 Insuficiente salida de aire Problema Causa Posible Remedio Problema Causa Posible Remedio La Localizaci n De Aver...

Reviews: