200990 - 4500W WIRELESS REMOTE START INVERTER GENERATOR
MAINTENANCE
33
Charge the Battery
For a generator equipped with batteries for electric starting,
proper battery maintenance and storage should be followed.
A trickle charger or battery maintainer should be used to charge
the battery while the generator is in storage. Maximum charging
rate should not exceed 1.6 amps. Follow the instructions included
with the trickle charger or battery maintainer. The battery should
be fully charged at least once per month.
1. Remove the battery from the generator.
2. Charge battery following the battery charger’s instructions.
3. After charging, leave the battery for 0.5 to 1 hour before
checking the voltage. If the voltage is less than 12.8 volts,
additional charging is necessary.
NOTICE
Electrolyte inside the battery is harmful to skin and eyes.
If the battery leaks and electrolyte gets in your eyes, do
not rub them. Instead, rinse them with clean running water
and immediately seek medical attention. If left untreated,
electrolyte can cause permanent eye injury.
NOTICE
–
Do not charge the battery with charging voltage over 15.0V
and charging current over 1.6A.
–
Do not charge the battery below 32°F (0°C) or above
113°F (45°C).
–
If the battery becomes hot to the touch, stop charging.
Allow battery to cool before resuming.
Remote Key fob battery
NOTICE
–
Always purchase the correct size and grade of battery
most suitable for the intended use.
–
Clean the battery contacts and also those of the device
prior to battery installation.
–
Remove batteries from equipment which is not to be used
for an extended period of time.
–
Remove batteries if consumed or if product is to be left
unused for a long time.
Adjusting the Governor
WARNING
Tampering with the factory set governor will void your
warranty.
The air-fuel mixture is not adjustable. Tampering with the governor
can damage your generator and your electrical devices and
will void your warranty. Contact our Technical Support Team at
1-877-338-0999 for all other service and/or adjustment needs.
Maintenance Schedule
Follow the service intervals indicated in the following maintenance
schedule.
Service your generator more frequently when operating in adverse
conditions.
Contact our Technical Support Team at 1-877-338-0999 to locate
the nearest CPE certified service dealer for your generator or
engine maintenance needs.
EVERY 8 HOURS OR PRIOR TO EACH USE
Check oil level
Clean around air intake and muffler
FIRST 5 HOURS (BREAK IN)
Change oil
EVERY 50 HOURS OR ANNUALLY
Clean air filter
Change oil if operating under heavy load or in hot
environments
EVERY 100 HOURS OR ANNUALLY
Change oil
Clean/adjust spark plug
Clean spark arrestor
Clean fuel valve filter*
EVERY 250 HOURS
Clean combustion chamber*
Check/adjust valve clearance*
EVERY 3 YEARS
Replace fuel line*
* To be performed by knowledgeable, experienced owners or CPE certified service
centers.