APPLICATION

The antenna isolation kit protects gate operator components from 
possible damage caused by certain wiring configurations. The 
installation of some accessories require one of the outputs from 
the transformer be shunted to the chassis ground which may blow 
the transformer fuse or damage the pre-installed universal 
receiver. LiftMaster

®

 does NOT recommend connecting the 

transformer outputs to the chassis ground, however some third 
party accessories require one of the transformer outputs to be 
shunted to the chassis ground.
The isolation kit is for use with gate operators models: SL575, 
SL585, SL595, HS670, SW420, SW279, and SW490.

CARTON INVENTORY

Nylon Flat Washer. . . . . . . . . . . . . . . . . . . . . . . . . . . . (216A0253)
Nylon Shoulder Washer  . . . . . . . . . . . . . . . . . . . . . . . (184A0182)
Fuse  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (35-310-032)
Fuse  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (35-310-032-1)

TOOLS NEEDED

•  Pliers and wrenches
• Screwdrivers
•  Diagonal wire cutters
• Wire strippers
• Drill 
•  1/2" drill bit
• Digital voltmeter

DETERMINE IF THE ISOLATION KIT IS NEEDED

To determine if the isolation kit is needed for your installation:
1.  Disconnect power to the operator.
2.  Disconnect the universal receiver (model 850LM) from the 

operator. Location varies depending on the operator, refer to 
the owner’s manual.

3.  Connect all other accessories according to the instructions 

that came with them.

4.  Restore power to the operator.
5.  Configure a digital voltmeter to measure AC voltage. Make 3 

voltage measurements between the following points: 

R1-R2

R1-chassis ground

, and 

R2-chassis ground

. Location varies 

depending on the operator, refer to the owner’s manual.

 

If there is no voltage between R1-R2, check to see if the 
transformer fuse is blown. If the fuse is blown, replace with 
the appropriate fuse included in the kit and measure voltage 
again.

6.  Refer to the table and follow the instructions indicated by 

your set of voltage measurements.

To reduce the risk of SERIOUS INJURY or DEATH:
•   Disconnect electric power at the fuse box BEFORE 

proceeding.

•   ALL electrical connections MUST be made by a qualified 

individual.

•   Upon completion of kit installation, the area MUST be 

cleared and secured. At that time the unit may be returned 
to service.

MEASUREMENT POINTS

VOLTAGE

INSTRUCTIONS

R1-R2

24 VAC

Neither of the 
transformer outputs are 
grounded. 

The isolation kit is NOT 
needed.

R1-chassis ground

Aprox. 
14 VAC

R2-chassis ground

Aprox. 
14 VAC

R1-R2

24 VAC

R1 is shunted to ground. 

Proceed to TEST THE 
UNIVERSAL RECEIVER 
FOR DAMAGE.

R1-chassis ground

0 VAC

R2-chassis ground

24 VAC

R1-R2

24 VAC

R2 is shunted to ground. 

Proceed to TEST THE 
UNIVERSAL RECEIVER 
FOR DAMAGE.

R1-chassis ground

24 VAC

R2-chassis ground

0 VAC

Antenna Isolation Kit

K001A3200-2

WARNING:

 This product can expose you to chemicals 

including lead, which are known to the State of California to 
cause cancer or birth defects or other reproductive harm. 
For more information go to 

www.P65Warnings.ca.gov

Summary of Contents for K001A3200-2

Page 1: ...er to measure AC voltage Make 3 voltage measurements between the following points R1 R2 R1 chassis ground and R2 chassis ground Location varies depending on the operator refer to the owner s manual If there is no voltage between R1 R2 check to see if the transformer fuse is blown If the fuse is blown replace with the appropriate fuse included in the kit and measure voltage again 6 Refer to the tab...

Page 2: ...r can be used INSTALL THE ISOLATION KIT To install the isolation kit 1 Disconnect power to the operator 2 Remove all accessories from the operator 3 Locate the chassis mounted F connector where the coax antenna passes through the operator chassis Location varies depending on the operator refer to the owner s manual 4 Disconnect the coax cables from both sides of the F connector 5 Remove the F conn...

Page 3: ...tension entre les points suivants R1 R2 R1 masse du châssis et R2 masse du châssis L emplacement varie en fonction de l actionneur consulter à cet effet le manuel du propriétaire S il n y a aucune tension entre R1 R2 vérifier si le fusible du transformateur est grillé Si le fusible est grillé le remplacer par le fusible approprié inclus dans le nécessaire et mesurer de nouveau la tension 6 Consult...

Page 4: ...é INSTALLER LE NÉCESSAIRE D ISOLATION Pour installer le nécessaire d isolation 1 Déconnecter l alimentation à l actionneur 2 Déposer tous les accessoires de l actionneur 3 Localiser le connecteur F monté sur le châssis où l antenne coaxiale passe par le châssis de l actionneur L emplacement varie en fonction de l actionneur consulter à cet effet le manuel du propriétaire 4 Déconnecter les câbles c...

Page 5: ...ltaje de corriente alterna Tomar tres medidas de voltaje entre los siguientes puntos R1 R2 R1 tierra de chasis y R2 tierra de chasis El lugar de instalación dependerá del tipo de operador Consultar el manual de instrucciones Si no se midiera voltaje entre R1 R2 verificar que el fusible del transformador no estuviera quemado Si el fusible estuviera quemado cambiarlo por el fusible del juego y volve...

Page 6: ...stalar el juego de aislamiento 1 Desconectar la alimentación eléctrica del operador 2 Desconectar todos los accesorios del operador 3 Ubicar el conector F montado en el chasis adonde la antena coaxial pasa por el chasis del operador El lugar de instalación dependerá del tipo de operador Consultar el manual de instrucciones 4 Desconectar los cables coaxiales de ambos lados del conector F 5 Quitar e...

Page 7: ...7 ...

Page 8: ... 2015 LiftMaster All Rights Reserved Tous droits réservés 01 37828B Todos los derechos reservados ...

Reviews: