background image

POSSIBLE CAUSES 

SOLUTONS 

UNIT DOES NOT START 

Unit may have become unplugged 
Fuse may have blown 
Circuit breaker may have been tripped 
Unit may be off 
Unit may be in a protection mode. 

Check that plug is plugged securely in wall receptacle. 

Note:

Plug has a test/reset button on it. Make sure that the plug has 

not tripped. 
Replace the fuse. See Note 1. 
Reset circuit breaker. See Note 1. 
Turn unit on (bottom right button on keypad). 

UNIT NOT COOLING/HEATING ROOM 

Unit air discharge section is blocked 
Temperature setting is not high or low 
enough 

Note: 

Setpoint limits may not allow the 

unit to heat or cool the room to the 
temperature desired. Check section on 
dipswitch settings. 
Unit air filters are dirty. 
Room is excessively hot or cold when 
unit is started. 
Vent door left open. 
Unit may be in a protection mode. 
Compressor is in time delay. 

Make sure that curtains, blinds or furniture are not restricting or 
blocking unit airflow. 
Reset to a lower or higher temperature setting. 
Remove and clean filters. 
Allow sufficient amount of time for unit to heat or cool the room. Start 
heating or cooling early before outdoor temperature, cooking heat or 
gatherings of people make room uncomfortable. 
Close vent door. 
Check dipswitch settings for desired comfort. 
Wait approximately 3 minutes for compressor to start. 

DISPLAY HAS STRANGE NUMBERS/ 

CHARACTERS ON IT 

The unit may be in a protection mode. 
The unit may be set for 

(instead of 

). 

UNIT MAKING NOISES 

Clicking, gurging and whooshing noises are normal during operation 
of unit. 

WATER DRIPPING OUTSIDE 

If a drain kit has not been installed, condensation runoff during very 
hot and humid weather is normal. See Note 2.If a drain kit has been 
installed and is connected to a drain system, check gaskets and 
fittings around drain for leaks and plugs. 

WATER DRIPPING INSIDE 

Wall sleeve is not installed level 

Wall sleeve must be installed level for proper drainage of 
condensation .Check that installation is level and make any 
necessary adjustments. 

ICE OR FROST FORMS ON INDOOR 

COIL 

Low outdoor temperature 
Dirty filters 

When outdoor temperature is approximately 55

  or below, frost 

may form on the indoor coil when unit is in Cooling mode. Switch unit 
to FAN operation until ice or frost melts. 
Remove and clean filters. 

COMPRESSOR PROTECTION 

Power may have cycled, so compressor 
is in a restart protection. 

Random Compressor restart-

Whenever the unit is plugged in,or 

power has been restarted,a random compressor restart will occur. 
After a power outage, the compressor will restart after approximately 
3 minutes. 

Compressor Protection-

To prevent short cycling of the compressor, 

there is a random startup delay of 3 minutes and a minimum 
compressor run time of 3 minutes. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES: 

1.If circuit breaker is tripped or fuse is blown more than once, contact a qualified electrician. 
2.If unit is installed where condensation drainage could drip in an undesirable location, an accessory drain kit 

should be installed and connected to drain system. 

 

 

 

 

 

cooperandhunter.us 28 

 

 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

Summary of Contents for CH-PT12HP1

Page 1: ...NDITIONER SERVICE MANUAL Model H PT12HP1 CH PT15HP1 H PT12HS2 CH PT15HS2 Designed by Cooper Hunter International Corporation Oregon USA www cooperandhunter com For proper operation please read and kee...

Page 2: ...otor 5 5 Operation of compressor 5 6 Dip switches and Jumper selection 5 7 Functions for Front desk switch panel and Wire Controller 6 Unit components 7 Installation details 7 1 How to install the uni...

Page 3: ...he product There is risk of fire or electric shock Install the panel and the cover of control box securely There is risk of fire of electric shock Always install a dedicated circuit and breaker Improp...

Page 4: ...ds There is risk of fire or electric shock Do not place a heater or other appliance near the power cable There is risk of fire and electric shock Do not allow water to run into electric parts It may c...

Page 5: ...failure or unintended operation Take care to ensure that nobody could step on or fall onto the outdoor unit This could result in personal injury and product damage CAUTION Always check for gas refrig...

Page 6: ...filter reduces the efficiency of the air conditioner and could cause product malfunction or damage Do not insert hands or other object through air inlet or outlet while the product is operated There...

Page 7: ...ntinuous mode HEAT The range of set temperature is 17 62 29 84 For heat pump models the unit can alternate to run between in reverse cycle heat mode and electric heater mode according to the differenc...

Page 8: ...tton the fan speed cycles through the settings as follows HIGH MED LOW HIGH DISPLAYS Shows the set temperature in or While on Fan only mode it shows the room temperature Control code LC Pads on the co...

Page 9: ...temperature sensor T3 oS Open or short circuit of outside temperature sensor T4 HS Open or short circuit of exhaust temperature sensor T5 or T6 Other codes LO Room temperature is lower than 0 32 HI Ro...

Page 10: ...nsion 2 no rear grille and rear net but include sleeve Dimension 3 include sleeve and rear net Dimension 4 include sleeve rear net and rear grille WxHxD mm WxHxD inch 1067x406x532 42 0x15 9x20 9 1067x...

Page 11: ...efrigeration system This will help to understand the refrigeration cycle and the flow of the refrigerant in the Heat Pump Cycle LIQUID SIDE HEAT EXCHANGE EVAPORATOR CHECK VALVE Heating Model only CAPI...

Page 12: ...ion 5 3 1 The compressor functions protection with a delay of three minutes 5 3 2 Sensor protection at open or short circuit 5 3 3 Evaporator anti freezing protection at cooling mode 5 4 Operation of...

Page 13: ...tes at the heat pump and cooling mode see FIG B T4 Operate on low speed T03 T04 Operate on high speed FIG B When T4 T03 and lasts for 1 minute the fan motor will operates at low speed When T4 T04 and...

Page 14: ...heater stop working 5 5 Operation of compressor 5 5 1 The compressor operates at cooling mode as below Operation condition T1 Ts 0 4 T1 Ts Compressor on Compressor off compressor on T1 Ts 4 compressor...

Page 15: ...be off If the T2 protection gets started the fan motor also does not work 5 5 2 2 The Heat pump operates as below The Heat pump s operation mode is in accordance with the way of compressor s working...

Page 16: ...n t be higher than 29 84 Electric Heat Only for heat pump unit only This setting is typically used for Emergency Heating Wall Thermostat Enable A wired wall thermostat can be connected to the unit If...

Page 17: ...nnect the units 2 Wired controller the digital LED will display LC Reserved if a wired controller is connected if the communication portal is one way the buttons on the control panel will be invalid N...

Page 18: ...of PTAC units x 1va Transformer Size va Example 110 PTAC units x1va 110va Transformer 2 Following are American Wire Gauge recommended sizes AWG WIRE SIZE NO 24 22 20 18 16 MAX LENGTH ft 400 600 900 1...

Page 19: ...figure 7 Installation details 7 1 How to install the unit iINSTALLATION CAUTION There are sharp edges that can cause serious cuts When lifting the air conditioner it is HEAVY Use 2 people to lift coop...

Page 20: ...the unit is installed securely and firmly When installing the sleeve make certain there is Dimension of air conditioner nothing within 20 of the back that would interfere with heat radiation and exhau...

Page 21: ...FRONT PANEL AND CASE Turn unit off and disconnect power supply To clean use water and a mild detergent Do not use bleach and abrasivers Some commercial cleaners may damage the plastic parts OUTDOOR C...

Page 22: ...t filter twice a year or as required Make sure to remove the shipping screw from the vent door See Fig 5 Rotate the vent control lever to open the vent door See Fig 6 Remove four screws from the vent...

Page 23: ...emp DB Indoor air temp DB 8 Operation characteristics 8 1 Cooling operation 45 40 35 30 25 20 5 10 15 20 25 30 35 40 Indoor air temp DB 8 2 Heating operation 35 30 25 20 15 5 5 15 25 Outdoor air temp...

Page 24: ...n reach of the service cord The standard cord connected 265V units require an accessory electrical subbase for operation Power Cord Protection The power cord for230 208v units provide power cord fire...

Page 25: ...t circuit of T3 temperature sensor oS Open or short circuit of T4 temperature sensor HS Open or short circuit of T5 or T6 temperature sensor Lo Temperature is lower than display range 0 32 HI Temperat...

Page 26: ...sampling voltage is lower than 0 06V or higher than 4 94V the LED will display the failure Supposed causes Wiring mistake Faulty sensor Faulty PCB Troubleshooting Check the connection between tempera...

Page 27: ...uses Wiring mistake Faulty display board Faulty main control board Troubleshooting cooperandhunter us 26 Communication malfunction between main control board and display board Check the signal wire be...

Page 28: ...speed GL HI FAN High fan speed GH 4 WAY 4 way valve for heat pump model B HEAT2 Electrical heater 2 W HEAT1 Electrical heater 1 W COMP Compressor Y 24V N 24VAC terminal N COM C 24V L 24VAC terminal L...

Page 29: ...may be set for instead of UNIT MAKING NOISES Clicking gurging and whooshing noises are normal during operation of unit WATER DRIPPING OUTSIDE If a drain kit has not been installed condensation runoff...

Page 30: ...8 82 8 7198 55 131 2 8442 2 35 6 31 5635 29 84 8 3357 56 133 2 7382 3 37 4 29 9058 30 86 7 9708 57 135 2 6368 4 39 2 28 3459 31 88 7 6241 58 136 2 5397 5 41 26 8778 32 90 7 2946 59 138 2 4468 6 42 8 2...

Page 31: ......

Reviews: