background image

C

GS TGC Installation, Operation & Maintenance

C

GS TGC v2 220322 

Basic Operation 

Isolate the equipment from all hazardous live power sources before opening the cover! 

When power is supplied to the TGC controller, the LED on the log of the cover will illuminate Red. To turn 
the TGC controller off, disconnect electrical power supply. 

The Status LED changes colour when the controller enters three (3) different states as follows. 

Green.

 Remains illuminated when gas is being supplied. 

Yellow.

 The controller LED will turn yellow ten (10) minutes before the automatic gas shut off 

timeout is reached and when five (5) minutes remain the buzzer will beep, and the yellow LED will 
then intermittently flash. After this time, the gas will automatically shut off until reactivated. 

Red.

 Remains illuminated when a remote emergency stop device has been activated.  

The gas supply is isolated until the emergency has been investigated, rectified, and reset. Press 
ON to re-enable/open the gas supply. 

Basic Maintenance 

Keep your gas controller in good working order - follow these basic principles. 

Remove any dust/debris from the outer enclosure regularly using a slightly damp cloth.

Never use detergents or solvents to clean your device.

Never spray air fresheners, hair spray, paint or other aerosols near the device.

Never paint the device.

Summary of Contents for CGS TGC

Page 1: ...ntroller Model CGS TGC Installation Operation Maintenance Manual Please read this manual carefully and retain for future use For specific requirements that may deviate from the information in this gui...

Page 2: ...rning Statements 3 Installation 4 Typical Application Location 4 Mounting Cabling 4 Circuit Board Terminals 5 Wiring Power Inputs 5 Wiring Gas Valve Outputs 6 Wiring Remote Emergency Stop 6 Selectable...

Page 3: ...be free of defects in material and workmanship for a period of twelve months 1 year from date of purchase The manufacturer s liability hereunder is limited to replacement of the product with repaired...

Page 4: ...status observation if intended for public use and is designed for indoor operation unless used in conjunction with a weatherproof cover sold separately Mounting Cabling If mounting direct to wall ensu...

Page 5: ...onnections to high voltage connectors Any damage attempting to remove the circuit board may void any warranty All Class 2 wiring is to be installed within flexible tubing to maintain segregation betwe...

Page 6: ...oller can be connected to remote devices with an open close circuit via the EM STOP volt free switch terminal This terminal has a factory fitted link installed normally closed circuit and when open wi...

Page 7: ...gas shut off timeout is reached and when five 5 minutes remain the buzzer will beep and the yellow LED will then intermittently flash After this time the gas will automatically shut off until reactiv...

Page 8: ...Not Formally Evaluated Operating 20 50 C 14 122 F 20 95 RH non condensing Storage 25 50 C 13 122F up to 95 RH non condensing Altitude Rating 2000m Wiring Typical Min 18AWG 75 C min Tinned copper Pre A...