Clear Weatherproof Covers
These indoor/outdoor low-profile covers protect devices
without restricting legitimate operation.
The versatile cover offers excellent protection against
physical damage (both accidental and intentional), dust
and grime as well as severe environmental conditions
inside and out.
Wall Mount Cover. Part No:
C
GS-TGC-WM-COVER
Flush Mount Cover. Part No:
C
GS-TGC-FM-
COVER
Contact your
C
GS Representative to order.
Circuit Board Terminals
Damage to PCBs when creating cable entry points may void any warranty!
Take care when making connections to high voltage connectors!
Any damage attempting to remove the circuit board may void any warranty!
All Class 2 wiring is to be installed within flexible tubing to maintain segregation between circuits!
Wiring of different circuits shall be separated by means of routing, clamping or barrier!
For field connections use wires suitable for at least 167°F (75°C)
Any parts that form part of the connections/installation must have a minimum fire-retardant rating of UL 94V-2!
Wiring
–
Power Inputs
The controller requires a power supply of 100-120V~ Wired to the [POWER/LINE IN] connector using a 3A
switched fused spur. Alternatively, the unit can be powered via the 24V [POWER IN] terminal. This can be
AC or DC.
When power is connected/live, a red LED will illuminate on the front of the controller on the
C
GS Logo.