CGS CGS TGC Installation, Operation & Maintenance Manual Download Page 5

C

GS TGC Installation, Operation & Maintenance

C

GS TGC v2 220322 

Clear Weatherproof Covers 

These indoor/outdoor low-profile covers protect devices 
without restricting legitimate operation.  

The versatile cover offers excellent protection against 
physical damage (both accidental and intentional), dust 
and grime as well as severe environmental conditions 
inside and out.  

Wall Mount Cover. Part No: 

C

GS-TGC-WM-COVER 

Flush Mount Cover. Part No: 

C

GS-TGC-FM-

COVER 

Contact your 

C

GS Representative to order. 

Circuit Board Terminals 

Damage to PCBs when creating cable entry points may void any warranty! 
Take care when making connections to high voltage connectors! 
Any damage attempting to remove the circuit board may void any warranty! 
All Class 2 wiring is to be installed within flexible tubing to maintain segregation between circuits! 
Wiring of different circuits shall be separated by means of routing, clamping or barrier! 
For field connections use wires suitable for at least 167°F (75°C) 
Any parts that form part of the connections/installation must have a minimum fire-retardant rating of UL 94V-2! 

Wiring 

 Power Inputs 

The controller requires a power supply of 100-120V~ Wired to the [POWER/LINE IN] connector using a 3A 
switched fused spur. Alternatively, the unit can be powered via the 24V [POWER IN] terminal. This can be 
AC or DC.  

When power is connected/live, a red LED will illuminate on the front of the controller on the 

C

GS Logo. 

Summary of Contents for CGS TGC

Page 1: ...ntroller Model CGS TGC Installation Operation Maintenance Manual Please read this manual carefully and retain for future use For specific requirements that may deviate from the information in this gui...

Page 2: ...rning Statements 3 Installation 4 Typical Application Location 4 Mounting Cabling 4 Circuit Board Terminals 5 Wiring Power Inputs 5 Wiring Gas Valve Outputs 6 Wiring Remote Emergency Stop 6 Selectable...

Page 3: ...be free of defects in material and workmanship for a period of twelve months 1 year from date of purchase The manufacturer s liability hereunder is limited to replacement of the product with repaired...

Page 4: ...status observation if intended for public use and is designed for indoor operation unless used in conjunction with a weatherproof cover sold separately Mounting Cabling If mounting direct to wall ensu...

Page 5: ...onnections to high voltage connectors Any damage attempting to remove the circuit board may void any warranty All Class 2 wiring is to be installed within flexible tubing to maintain segregation betwe...

Page 6: ...oller can be connected to remote devices with an open close circuit via the EM STOP volt free switch terminal This terminal has a factory fitted link installed normally closed circuit and when open wi...

Page 7: ...gas shut off timeout is reached and when five 5 minutes remain the buzzer will beep and the yellow LED will then intermittently flash After this time the gas will automatically shut off until reactiv...

Page 8: ...Not Formally Evaluated Operating 20 50 C 14 122 F 20 95 RH non condensing Storage 25 50 C 13 122F up to 95 RH non condensing Altitude Rating 2000m Wiring Typical Min 18AWG 75 C min Tinned copper Pre A...