GS TGC Installation, Operation & Maintenance

C

GS TGC v2 220322 

Wiring 

 Gas Valve Outputs 

A gas solenoid valve should be powered using one of the terminals marked [VALVE OUT]. 
Terminals offer control via mains 100-120V~ or 24V~ 

When wired to a normally closed gas solenoid valve, the TGC controller can be used to isolate the gas 
supply either by; pressing the Off button on the unit; when the configured time runs out or if remote 
emergency devices are activated. 

Wiring 

 Remote Emergency Stop 

The Timed Gas Controller can be connected to remote devices with an open /close circuit via the [EM 
STOP] volt free switch terminal.  

This terminal has a factory fitted link installed (normally closed circuit) and when open will isolate the gas 
supply resetting the gas supply timer. No audible alarm will occur 

 only EM Stop LED indicator. 

Selectable Automatic Timeout Switches 

On the circuit board are two dipswitches used for selecting the automatic gas shutoff timeout. 

The controller LED will turn yellow ten (10) minutes before the selected time is reached and when five (5) 
minutes remain the buzzer will beep, and the yellow LED will then intermittently flash.  

After this time, the gas will automatically shut off until reactivated. 

Summary of Contents for CGS TGC

Page 1: ...ntroller Model CGS TGC Installation Operation Maintenance Manual Please read this manual carefully and retain for future use For specific requirements that may deviate from the information in this gui...

Page 2: ...rning Statements 3 Installation 4 Typical Application Location 4 Mounting Cabling 4 Circuit Board Terminals 5 Wiring Power Inputs 5 Wiring Gas Valve Outputs 6 Wiring Remote Emergency Stop 6 Selectable...

Page 3: ...be free of defects in material and workmanship for a period of twelve months 1 year from date of purchase The manufacturer s liability hereunder is limited to replacement of the product with repaired...

Page 4: ...status observation if intended for public use and is designed for indoor operation unless used in conjunction with a weatherproof cover sold separately Mounting Cabling If mounting direct to wall ensu...

Page 5: ...onnections to high voltage connectors Any damage attempting to remove the circuit board may void any warranty All Class 2 wiring is to be installed within flexible tubing to maintain segregation betwe...

Page 6: ...oller can be connected to remote devices with an open close circuit via the EM STOP volt free switch terminal This terminal has a factory fitted link installed normally closed circuit and when open wi...

Page 7: ...gas shut off timeout is reached and when five 5 minutes remain the buzzer will beep and the yellow LED will then intermittently flash After this time the gas will automatically shut off until reactiv...

Page 8: ...Not Formally Evaluated Operating 20 50 C 14 122 F 20 95 RH non condensing Storage 25 50 C 13 122F up to 95 RH non condensing Altitude Rating 2000m Wiring Typical Min 18AWG 75 C min Tinned copper Pre A...

Reviews: