Cetetherm Midi Wall IQHeat
Installation, service and operating instruction
12
4.1
Password and login
The controller has password protection, allowing access to different menus.
The following log-in levels are available:
All users: no log-in, no password required
•
read access to all menus except the system parameters, configuration and detail menus
•
read access to alarm lists and alarm history
End user, level 6, password 1000
•
appears with one key in the upper left corner of the display
•
all rights as for in "all users"
•
read access to all menus except configuration menus
•
write access to the main set points (Setpoints/Settings. > Setpoints)
•
alarms and alarm history can be acknowledged and reset
Service level, level 4, password 2000
Used for configuring I/Os and system settings. Only qualified service personnel should make changes at this
level.
•
appears with two keys in the upper left corner of the display
•
all rights as for "End users"
•
access to all menus except I/O configuration and system settings
OEM, level 2
•
appears with three keys in the upper left corner of the display
•
all rights as for System Administrator
•
access to all menus and system settings.
Contact Cetetherm if there is a need to change anything at this level.