Cetetherm Midi Wall IQHeat
Installation, service and operating instruction
15
6
Electrical installation
6.1
General
The wiring in Midi Wall conforms to the applicable rules for CE marking and has undergone electrical safety
testing and function testing. For permanent installation must the substation be connected to an all-pole isolator
switch. This must be done by a duly qualified electrician.
The substation must be connected to a grounded power outlet.
6.2
Connection to internet
For connection to internet the control panel has a cable with RJ45-contact.
6.3
Installation of outdoor temperature sensor
Connect the outdoor temperature sensor to a terminal strip in accordance with the
electrical diagram, if there is a resistor, remove it.
The resistor simulates an outdoor temperature of 0°C.
If using a cable with two conductor area of 0.75mm
2
the maximum cable length is
80 meters.