background image

Revision Date: July 24, 2020 

 

Wiring

 

Diagrams

 

 

3P4W with 3CTs

 

 

3P3W with 3CTs

 

 

3P3W with 2CTs

 

 

3P4W with 3PTs, 3CTs

 

 

3P3W with 2PTs, 3CTs

 

 

3P3W with 2PTs, 2CTs

 

 

 

1P3W with 2CTs

 

1P2W Uln with 1CT

 

1P2W Ull with 1CT

 

3x1P with 3CTs

 

Basic Setup Parameters 

Menu 

Parameters 

Description 

Range/Options 

Default 

SYS SET 

Wiring Mode 

The wiring connection of the meter 

0=DEMO, 1=1P2W L-N, 2=1P2W L-L,   

3=1P3W L-L-N, 4=3P3W, 5=3P4W, 

6=3P3W_2CT, 7=1x3P 

5=3P4W 

PT Primary 

Primary PT Ratio 

1 to 1,000,000V 

381 

PT Secondary 

Secondary PT Ratio 

1 to 690V 

381 

CT Primary 

Primary CT Ratio 

1 to 30,000 (A) 

5A 

CT Secondary 

Secondary CT Ratio 

1 to 5 (A)/100A 

5A 

Ia Polarity 

Reverse Phase A CT Polarity 

YES/NO 

NO 

Ib Polarity 

Reverse Phase B CT Polarity 

YES/NO 

NO 

Ic Polarity 

Reverse Phase C CT Polarity 

YES/NO 

NO 

COM SET 

Unit ID 

Unit ID 

1-247 

100 

Baud rate 

Data rate in bits per second 

1200/2400/4800/9600/19200/38400bps 

9600 

Comm. Config. 

Data Format 

8N2/8O1/8E1/8N1/8O2/8E2 

8E1 

Transparent 

LoRa Gateway 

0=Disabled, 1=Enabled 

LoRa Band 

Band of LoRa 

EU863-870, RU864-870, IN865-867,   

US902-928, AU915-928, AS920-923, AS923-925 

AS923-925 

LoRa Channel 

Channel of LoRa 

0~15   

0 (923.00) 

 