User Setting String Description:
The following table shows the options that can be changed by the user:
Table4. User Setting String
OPV
Output voltage mode selection
[220]= 220V
[230]= 230V
[240]= 240V
AVR
Input type selection
[000]= Normal range mode
[001]= Wide range mode
[002]= Generator mode
EbM
External battery module (EBM) settings 0~9 is the number of external battery
module(s)
TEST Auto self-test function
[000]=Disable[001]=Enable
AR
Automatic restart
[000]=Disable[001]=Enable
GF
Green function
[000]=Disable[001]=Enable
bZ
Buzzer control
[000]=Disable[001]=Enable
LS1
Load segment 1
[000]=Turn off[001]=Turn on
LS2
Load segment 2
[000]=Turn off[001]=Turn on
4.2 Operating Mode
Normal range mode: The UPS accepts an AC input voltage within the range of
+/-20%.
Generator mode: The low frequency transfer point of the UPS can go as low
as 40Hz and as high as 70Hz before being transferred to battery mode.
Wide range mode: The UPS accepts an AC input voltage within the range of
-30% ~ +20%.