SENSOR CM2K
6+ CIRCUIT
E111
th
Possible cause:
Interruption
in the cables between the 6
circuit sensor and CM2K, connections on the CM2K,
c
old
junction or defective sensor.
th
Boiler status:
The boiler operates normally, the 6 CM2K
circuit stops to operate, stops (turns off) the pump.
Troubleshooting:
Call an authorized serviceman who will
check the sensor position, check the damage/accuracy of the
sensor and cable , check the contacts on the
c
onnectors ,
check the sensor's ohm resistance.
CORRECTOR CM2K
6+ CIRCUIT
E112
th
Possible cause:
Interruption
in the cables between the 6
circuit corrector and CM2K, connections on the CM2K, cold
junction or defective corrector
th
Boiler status:
The boiler operates normally, the 6 CM2K
circuit continues to operate as if the corrector is turned off.
Troubleshooting
:
Call an authorized serviceman who will
check the corrector position , ch
e
ck the damage/accuracy of
the corrector and cable, check the contacts on the connectors.
SENSOR CM2K
7+ CIRCUIT
E113
th
Possible cause:
Interruption
in the cables between the 7
circuit sensor and CM2K,
connections on the CM2K, cold
junction or defective sensor.
th
Boiler status:
The boiler operates normally, the 7 CM2K
circuit stops to operate, stops (turns off) the pump.
Troubleshooting:
Call an authorized serviceman who will
check the sensor position, check the damage/accuracy of the
sensor and cable, check the contacts on the connectors, check
the sensor's ohm resistance.
CORRECTOR CM2K
7+ CIRCUIT
E114
th
Possible cause:
Interruption
in the cables between the 7
circuit corrector and CM2K, connections on the CM2K, cold
junction or defective corrector
th
Boiler status:
The boiler operates normally, the 7 CM2K
circuit continues to operate as if the corrector is turned off.
Troubleshooting:
Call an authorized serviceman who will
check the corrector position, check the damage/accuracy of the
corrector and cable, check the contacts on the connectors.
SENSOR CM2K
8+ CIRCUIT
E115
th
Possible cause:
Interruption
in the cables between the 8
circuit sensor and CM2K
,
connections on the CM2K, cold
junction or defective sensor.
th
Boiler status:
The boiler operates normally, the 8 CM2K
circuit stops to operate, stops (turns off) the pump.
Troubleshooting:
Call an authorized serviceman who will
check the sensor position, check the damage/accuracy of the
sensor and cable, check the contacts on the
c
onnectors, check
the sensor's ohm resistance.
CORRECTOR CM2K
8+ CIRCUIT
E116
th
Possible cause:
Interruption
in the cables between the 8
circuit corrector and CM2K, connections on the CM2K, cold
junction or defective corrector
th
Boiler status:
The boiler operates normally, the 8 CM2K
circuit continues to operate as if the corrector is turned off.
Troubleshooting:
Call an authorized serviceman who will
check the corrector position, check the damage/accuracy of the
corrector and cable, check the contacts on the connectors.
Errors
Technical instructions CONTROLLER -
CPREG-Touch
101