Technical instructions CONTROLLER -
CPREG-Touch
100
Errors
SENSOR CM2K
3+ CIRCUIT
E105
rd
Possible cause:
Interruption
in the cables between the 3
circuit sensor and CM2K, connections on the CM2K, cold
junction or defective sensor
rd
Boiler status:
The boiler operates normally, the 3 CM2K circuit
stops to operate, stops (turns off) the pump.
Troubleshooting:
Call an authorized serviceman who will
check the sensor position, check the damage/accuracy of the
sensor and cable, check the contacts on the
c
onnectors, check
the sensor's ohm resistance.
CORRECTOR CM2K
3+ CIRCUIT
E106
rd
Possible cause:
Interruption
in the cables between the 3
circuit corrector and CM2K, connections on the CM2K, cold
junction or defective corrector.
rd
Boiler status:
The boiler operates normally, the 3 CM2K
circuit continues to operate as if the corrector is turned off.
Troubleshooting:
Call an authorized serviceman who will
check the corrector position, check the damage/accuracy of the
corrector and cable, check the contacts on the connectors.
SENSOR CM2K
4+ CIRCUIT
E107
th
Possible cause:
Interruption
in the cables between the 4
circuit sensor and CM2K, connections on the CM2K, cold
junction or defective sensor.
th
Boiler status:
The boiler operates normally, the 4 CM2K
circuit stops to operate, stops (turns off) the pump.
Troubleshooting:
Call an authorized serviceman who will
check the sensor position , check the damage/accuracy of the
sensor and cable, check the contacts on the connectors, check
the sensor's ohm resistance.
CORRECTOR CM2K
4+ CIRCUIT
E108
th
Possible cause:
Interruption
in the cables between the 4
circuit corrector and CM2K, connections on the CM2K , cold
junction or defective corrector
th
Boiler status:
The boiler operates normally, the 4 CM2K
circuit continues to operate as if the corrector is turned off.
Troubleshooting:
Call an authorized serviceman who will
check the corrector position, check the damage/accuracy
of the
corrector and cable, check the contacts on the connectors.
SENSOR CM2K
5+ CIRCUIT
E109
th
Possible cause:
Interruption
in the cables between the 5
circuit sensor and CM2K, connections on the CM2K, cold
junction or defective sensor
th
Boiler status:
The boiler operates normally, the 5 CM2K
circuit stops to operate, stops (turns off) the pump.
Troubleshooting:
Call an authorized serviceman who will
check the sensor position, check the damage/accuracy of the
sensor and cable, check the contacts on the
c
onnectors, check
the sensor's ohm resistance.
CORRECTOR CM2K
5+ CIRCUIT
E110
th
Possible cause:
Interruption
in the cables between the 5
circuit corrector and CM2K, connections on the CM2K, cold
junction or defective corrector
th
Boiler status:
The boiler operates normally, the 5 CM2K
circuit continues to operate as if the corrector is turned off.
Troubleshooting:
Call an authorized serviceman who will
check the corrector position, check the damage/accuracy of the
corrector and cable, check the contacts on the connectors.