FIRESTAR COMBUSTION CONTROLLER - VERSION 6.7 • OPERATION MANUAL
Door Open
Status
Fan
Primary
Secondary Connected
Power
IGNITION
AIR
LED RED
Opening the furnace door automatically places the furnace in Door Open
Mode. In this mode, if the Reaction Chamber is above 550˚F, the primary air
actuator is closed, the combustion fan is on, and the secondary air actuator is
open to continually vent gases from the Reaction Chamber until it cools to less
than 550˚F. The Secondary status LED will be illuminated while the actuator is
open. DOOR OPEN will be displayed in the LED display.
Ignition Air
Status
Fan
Primary
Secondary Connected
Power
IGNITION
AIR
LED RED
When the water temperature is below the water temperature setpoint, the
furnace firebox door is open and the Ignition Air button is pressed, the primary
air actuator will open. This will provide air to the upper section of the firebox,
helping to ignite a new fuel load. The Primary status LED will display a red
light. To exit this mode, close the furnace firebox door or turn the controller off
and back on.