FIRESTAR COMBUSTION CONTROLLER - VERSION 6.7 • OPERATION MANUAL

LED Display Alarm Definitions

The LED display will display an alarm message when abnormal conditions 

appear. If any of the following messages appear, take corrective action.

FIRE OUT

When the system is calling for heat, if the temperature in the Reaction 

Chamber has been below 300˚F for 60 minutes and does not rise more than 

5˚F, or after three hours even if the temperature is rising, the combustion 

fan will turn off and the primary air actuator will close. This alarm is reset by 

opening and closing the furnace door, or by turning the controller off and back 

on.

HIGH TEMP1

The temperature sensor connected to the FireStar combustion controller 

has detected that the water temperature is above 200˚F. The controller will 

continue to alternate between HIGH TEMP1, the water temperature, and the 

Reaction Chamber temperature until it senses that the water temperature has 

fallen below 195˚F.

HIGH TEMP2

The external high limit sensor has sensed that the water temperature is above 

200˚F and has disconnected power to the combustion fan and actuators. 

The controller will continue to alternate between HIGH TEMP2, the water 

temperature, and the Reaction Chamber temperature until it senses that the 

external sensor has reconnected power. This will normally happen when the 

sensor cools to 165˚F.

If this alarm occurs often, lower the water temperature setpoint.

LOW WATER

Check the water level at the sight gauge and, if necessary, add water according 

to the Water Quality and Maintenance section of the Owner’s Manual. If 

adding water does not clear the LOW WATER alarm, it can be temporarily 

overridden until a repair can be made (see the Setup Mode section, variable 

#18).

NOTE: If water is added to the outdoor furnace and/or system, the system water should 

be tested and 1650XL Inhibitor Plus should be added (if necessary) to maintain the 

recommended level of protection.

Summary of Contents for Fire Star

Page 1: ...ER Save This Manual For Future Reference 1 AUG 2018 p n 9000645 For parts and accessories service or repairs call your authorized Central Boiler dealer or heating contractor Record the information bel...

Page 2: ......

Page 3: ...5 Standby Idle 5 Idle Pulse 6 Demand Mode Low 6 Demand Mode Medium 6 Demand Mode High 7 IdleTransition Mode 7 Door Open 8 Ignition Air 8 Basic Controller Features 9 AdjustingWaterTemperature Setpoint...

Page 4: ...sage to alert you Before operating the FireStar Combustion Controller become familiar with the information the control panel provides and with the procedures for making changes to settings 1 Power but...

Page 5: ...actuator will open helping to light the fire in the firebox Outdoor Furnace Operation Power When the controller is off the LED display will be off To turn the controller on or off press the Power butt...

Page 6: ...Temperature Setpoint minus the Water Temperature Differential the controller will enter Demand Mode In Demand Mode the primary air actuator will slowly open to the correct setting for the furnace mod...

Page 7: ...Status Fan Primary Secondary Connected Power IGNITION AIR As the water temperature setpoint is reached in Demand Mode the primary air actuator will close to stop combustion and the Primary status LED...

Page 8: ...cools to less than 550 F The Secondary status LED will be illuminated while the actuator is open DOOR OPEN will be displayed in the LED display Ignition Air Status Fan Primary Secondary Connected Pow...

Page 9: ...ton at the same time This monitor will reset to 00 00 each time the furnace is loaded with wood i e the firebox door is left open for more than 30 seconds To manually reset this monitor press the Igni...

Page 10: ...ter temperature displays for 6 seconds and the combustion temperature in the Reaction Chamber displays for 3 seconds during normal operation To briefly display the Reaction Chamber temperature press t...

Page 11: ...ble to the desired setting Press the Menu button to save the setting and return to Setup Mode To Exit Setup Mode Wait 10 seconds without pressing any buttons and the controller will automatically exit...

Page 12: ...ERATURE The idle pulse will continue until the temperature in the Reaction Chamber is above this temperature To effectively disable the pulse to temperature feature lower this value to its minimum set...

Page 13: ...te furnace operation will stop and the display will flash special characters to indicate the update process The entire process should take about 5 minutes Do not disconnect power during this process I...

Page 14: ...en for more than 30 seconds This will allow operation for one loading must override each loading until a repair can be made Do not override this alarm if the system has a leak NOTE If water is added t...

Page 15: ...ction Chamber temperature until it senses that the water temperature has fallen below 195 F HIGHTEMP2 The external high limit sensor has sensed that the water temperature is above 200 F and has discon...

Page 16: ...er BYPASS The bypass door is open if applicable to your model DOOR OPEN The firebox door is open TC1 TC2 TC3 or A 1 If the display indicates any of these messages contact your dealer STEP FAIL 1 STEP...

Page 17: ...a 1 4 nut driver or socket remove the two screws and open the control panel 3 Remove the round plug on the left side of the control 4 Install the grommet into the hole 5 Align the antenna through the...

Page 18: ...n LED will flash blue while it is attempting to connect When the LED is a steady green the control is connected to your network 15 If the control fails to connect the connection LED will be steady red...

Reviews: