17. Auto-Assigned ID
This variable stores an auto-assigned ID number for
communication between your FireStar II controller and
your FireStar XP.
18. Technician Use Only: 1
Do not adjust this value.
19. Electric Assist Duration: 0 (wood pellets)
61 (corn)
Time in minutes that the electric ignitor(s) will remain
on after Ignition Required Temperature (variable 4) has
been met. Setting this variable to 61 will keep the electric
ignitor(s) on constantly. Adjustable from 0 to 61.
20. Ignition Prime Duration: 15 (wood pellets)
2 (corn)
The augers will run for this amount of time in seconds
during the first ignition attempt. Adjustable from 0 to 255.
21. 2nd Ignition Prime Duration: 30 (wood pellets)
1 (corn)
The augers will run for this amount of time in seconds
during the second ignition attempt. Adjustable from 0 to
255.